background image

15

4. For connection at the core processor housing, prepare shielded cable

as follows (for armored cable, omit steps d, e, f, g):

a.

Strip 4 1/2 inches (114 mm) of cable jacket.

b.

Remove the clear wrap that is inside the cable jacket, and remove
the filler material between the wires.

c.

Remove the foil shield that is around the insulated wires, leaving
3/4 inch (19 mm) of foil or braid and drain wires exposed, and
separate the wires.

d. Wrap the shield drain wire(s) around the exposed foil twice. Cut

off the excess wire.

e.

Place the shielded heat shrink over the exposed shield drain
wire(s). The tubing should completely cover the drain wires.

f.

Without burning the cable, apply heat (250 °F or 120 °C) to shrink
the tubing.

4 1/2 in

(114 mm)

3/4 in

(19 mm)

7/8 in

(22 mm)

7/8 in

(22 mm)

Shielded

heat shrink

Gland body

Gland nut

Gland clamping

insert

Shield drain wire(s) wrapped twice around exposed shield foil