4.3.1 Conditions for Parallel System

• Each UPS module must have the same bypass source.
• The outputs of all UPS modules are connected altogether.
• The main inputs can be from different sources, but the phase rotation sequence of main inputs,

bypass inputs and outputs must be correct and the same.

• The parallel logic cable and load sharing cable must be connected in a ring correctly (see

Figure 17).

4.3.2 Cabinet Installation

Parallel system composed of two or more UPS modules using parallel cabinet
The UPS modules that will form the parallel system should be placed side-by-side. Each battery cabi-

net is placed next to its corresponding UPS module.
The parallel cabinet should be placed in the middle of the system.

4.3.3 Preliminary Checks

Each UPS module should have the same firmware and the same hardware version. Refer to the

instructions in 4.3.1 - Conditions for Parallel System.

4.3.4 Power Cables

Wiring of power cables is similar to that of a single module system (See 2.1 - Power Cabling). The

bypass sources of all modules should be the same, and the outputs should be connected altogether cor-

rectly.
Power cables are field-supplied. Power cables to the UPS’s of the paralleling cabinet must be routed

through either the top or bottom entry access of the UPS.

4.3.5 Parallel Control Cables

Parallel System Control Cables

Make the connections listed below on the parallel logic board (M3) inside the Liebert NX. (See

Figure 23 for the location of the parallel logic board):
Shielded and double-insulated control cables, available in lengths of up to 100 feet (30m), must be

interconnected in a ring configuration between UPS modules as shown below. The ring configuration

ensures high reliability of the control (refer to Figure 17).

NOTE
When paralleling UPS's with different power ratings, the power rating of the largest UPS can

be no more than four times the power rating of the smallest UPS

NOTE
The system input and/or output circuit breaker is to be field-supplied. See Table 8 for current

rating.

NOTE
The length and specifications of power cables including the bypass input cables and UPS

output cables should be the same, thus the load can be shared evenly in bypass mode.