Emerson SiteI/O 32/0 User Manual

Emerson Hardware

Advertising
background image

Specification for SiteI/O 32/0


DESCRIPTION:
The SiteI/O 32/0 is part of the SiteI/O-Line, which allows a complete SiteScan
monitoring/control system to be built a piece at a time. It is a 32 bit microprocessor-based device
designed to monitor up to thirty-two analog, digital, and/or dry contact type signals. Individual hardware
jumpers set signal-type selections. Screw terminal blocks are provided to terminate power,
communication, and input signal wiring.

DIMENSIONS:

Module:

11 5/16” H x 11 5/16” W x 2 3/4” D

28.73 cm H x 28.73 cm W x 7 cm D


Enclosure:

20" H x 18" W x 2.87" D

(Painted Steel)

508mm x 457.2mm x 72.89mm


See Enclosure Diagrams for mounting options.


POWER: 24VAC

± 10%, 50-60 Hz., 35 VA power consumption

(120/24VAC 40VA Transformer available)


INPUTS:

Thirty-two universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor.


ENVIRONMENTAL
OPERATING RANGE:
0

° to 130° F (-17.8° to 54.4° C), 10 to 90% relative humidity, non-condensing


COMMUNICATION:

(1) CMnet EIA-485 Port - Control Module network screw terminals

Switch selectable baud rates ARC156 / 9600 or 38.4bps
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2


(32) Analog and/or Digital - screw terminals

Jumper Selectable inputs

Thermistor - 10k ohm @ 77

° F, 25°C

0 to 5 VDC - 10k ohm max source impedance

4 to 20mA - 24VDC loop power, 250 ohm input

Dry Contact - 0.5mA sense current


MEMORY:

1 MB Flash Memory, 1 MB Non-volatile battery backed RAM.


PROTECTION:

Voltage, current, and ESD protection on incoming power.

Liebert Corporation

Page 1 of 5 SL-28073 Rev. 4; 7/03

Advertising