Initial installation – Enviro Sienna Indoor Gas Fireplace User Manual

Page 14

Advertising
background image

14

Initial Installation

Check draft with a match

or smoke in a 1⁄4" (6 mm)

tube located here.

M

INIMUM

F

IREPLACE

S

IZE

:

Description of Fireplace Dimension

Direct Vent

B-Vent

Width

At Back

23 1⁄4” (591 mm)

23 1⁄4” (591 mm)

At Front

35” (889 mm)

35” (889 mm)

Height

With Surround Only

23 3⁄4” (603 mm)

23 3⁄4” (603 mm)

With Surround with Trim

23” (584 mm)

23” (584 mm)

Depth

With Surround Only

18” (457 mm)

19” (483 mm)

With Surround with Trim

16 1⁄2” (419 mm)

17 1⁄2” (445 mm)

B-V

ENT

M

ODEL

:

WARNING: This appliance has been designed to operate by drawing combustion air and dilution air

from the room. It is also designed to draw room air for proper heat circulation from the sides of the

unit. Blocking or modifying the louvers in any way can create hazardous situations, either through poor

venting or by overheating. It is important that this unit has sufficient air circulation for proper venting

and combustion. Provisions must be made for the supply of adequate combustion and ventilation air.

These openings must not be blocked. The appliance must not be connected to a chimney flue servicing

a separate solid fuel-burning appliance.

A

UTOMATIC

F

LUE

G

AS

S

PILL

S

WITCH

- B-V

ENT

M

ODEL

O

NLY

:

NOTE: This heater must be properly connected to a venting system. This heater is equipped

with a vent safety shutoff system designed to protect against improper venting of combustion

products. This safety switch is located on the rear of the appliance. If the switch trips more

than once, the venting should be inspected by a qualified service technician for possible

blockage or severe down draft conditions.

WARNING: Operation of this heater when not connected to a properly installed and maintained

venting system can result in carbon monoxide (CO) poisoning and possible death.

The draft hood must be in the same pressure zone as

the air inlet. Inspect for draft from the front of the unit

at the 1⁄4” tube shown in Figure 18. Check for a draft

using smoke; a vacuum or suction into the tube will

indicate proper drafting. If air is blowing out of the tube

the problem must be corrected before the unit can be

started.
This model can be vented with 4” aluminum or stainless

steel flex vent and/or certified Type B Gas Vent. The

flue collar of the appliance will fit inside of a standard

4” vent and may be fastened directly to the vent. Check

periodically that the vent is unrestricted and an adequate

draft is present when the unit is in operation.

Figure 18: Draft check.

Table 3: Minimum dimensions of fireplace for Sienna to be installed into.