Emerson 40-120KVA User Manual

Va, 60h, 480vac - s, Iebert

Advertising
background image

1

The Liebert NX is a true on-line, double conversion,

three-phase UPS system that delivers complete,

centralized power protection for mission-critical

systems.

Designed to meet the high availability power needs

of a wide variety of IT applications, the UPS com-

bines a rack form factor, advanced operating fea-

tures and low cost of ownership.
• Increases growth flexibility with Softscale™

technology, plus the ability to parallel modules

for increased capacity and redundancy.

• Achieves higher availability by reducing the

number of UPS units required to power your

data center.

• Reduces total cost of ownership through the use

of longer life batteries and simplified preventive

maintenance.

OUTPUT

Voltage

480VAC, 60Hz,
3-phase, 3-wire plus ground

Voltage
Adjustment
Range

±5%

Voltage
Regulation

1% for balanced load
2% for 100% unbalanced load

Dynamic
Regulation

±5% deviation for 100% load step
±1% for loss or return of AC input

Transient
Response Time

Recover to ±5% of output voltage
within 1/2 cycle

Voltage
Distortion

For linear loads, 1% THD
Less than 4% THD for 100% nonlinear
loads without kVA/kW derating

Phasing
Balance

120° ±0.5° for balanced load
120° ±1° for 100% unbalanced load

Frequency
Regulation

±0.05% single module
±0.25% paralleled modules

Load Power
Factor Range

0.5 lagging to 1.0 without derating

Overload

125% of full load for 10 minutes
150% for one minute, with true
sinusoidal waveform

STANDARDS
Listed to UL 1778 UPS standards, and CSA certified.
Meets current requirements for safe high performance
UPS operation.

L

IEBERT

®

NX

3-P

HASE

UPS: 40-120

K

VA, 60H

Z

, 480VAC - S

ITE

P

LANNING

D

ATA

External Battery Cabinet

Battery

Manufacturer

Battery

Type

Dimensions

in. (mm)

Weight
lb. (kg)

Qty.

Battery

Cabinets

Battery Time (minutes)

40kVA 60kVA 80kVA 100kVA 120kVA

C&D

Technologies

UPS12-100MR

35.3x38.2x78.7

(897x970x2000)

1750

(794)

1

5

2

17

9

5

UPS12-150MR

2000

(907)

1

12

7

2

33

20

13

9

7

UPS12-210MR

2500

(1134)

1

19

11

6

2

48

31

21

15

11

Enersys

HX205

35.3x38.2x78.7

(897x970x2000)

2620

(1188)

1

19

11

7

2

46

28

20

15

12

General Specifications

INPUT

Voltage

480VAC, 60Hz
3-phase, 3-wire plus ground

Voltage Range
without derating

+15%, -25%

Frequency Range

57-63Hz

Current
Distortion

3% maximum reflected THD
at full load

Current Limit

140% of full load input current

Current
Walk-In

20 seconds to full load
Programmable, 0 to 30 seconds

Power Factor

>0.99 lagging at full load
>0.98 lagging at half load

Surge
Protection

Sustains input surges without damage,
per criteria listed in IEC 61000-4-5

ENVIRONMENTAL
Operating
Temperature

UPS: 32° to 104°F (0-40°C)
Battery: 68° to 86°F (20-30°C)

Non-Operating
Temperature

-13° to 158°F
(-25° to 70°C)

Relative Humidity

0-95% non-condensing

Operating
Altitude

Up to 6,500 ft. (2,000m)
without derating

Acoustical Noise (full load)

80kVA

<67dB at 80-104°F (27-40°C) ambient
<61dB below 80°F (27°C) ambient

120kVA

<69dB at 80-104°F (27-40°C) ambient
<63dB below 80°F (27°C) ambient

Advertising