Model ei144 heat, Installation & placement, Technical specification – Ei Electronics Ei144 User Manual

Page 2

Advertising
background image

Shannon Free Zone, Shannon, Co. Clare, Ireland.

Ph.

+353 61 471277

Fx.

+353 61 471053

Email.

[email protected]

Web:

www.eielectronics.com

E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice

.

Ei144 DataSht RevA


Model

Ei144 Heat

Installation & Placement

Wiring for Interconnected Alarms

Be very careful about correctly wiring the alarms as mixing Live and Neutral
will blow/damage interconnected alarms.

Locate heat alarms in rooms adjoining or on escape routes

– kitchens,

garages, boiler houses etc. where smoke alarms are unsuitable. Install within
5.3m of potential sources of fire.

Please consult instruction booklet for specific installation details

Important Precaution:

Do not install the actual smoke/heat
alarm itself in new or renovated
buildings until all work is completed
(including floor coverings) and the
building has been fully cleaned.
The wiring can be installed when
appropriate. (Excessive dust and
debris from building work can
contaminate the smoke chamber
and cause problems, and it will also
invalidate the guarantee). If it must
be installed, cover it completely,
particularly around the edges, with
a dust cover (eg. a plastic bag),
until all cleaning is finished..
Connect wires to the unit as in
wiring diagram. All wiring must
comply with local codes.

Technical Specification

Sensor

Thermistor


Sensitivity:

Complies with BS 5446 Part 2:
2003


Source:

Contains no radioactive material


Airspeed:

Essentially immune to the effect

of airspeed.


Button Test:

Simulates the effect of heat and
checks electronics and horn.


Supply Voltage:

230V AC


Battery back up:

9V Alkaline Battery


Power-On Indicator:

Continuous green LED


Alarm:

Electronic Piezoelectric horn
in unit


Alarm Sound Output:

85dB (minimum) at 3m


Alarm Status:

Red LED flashes every second on

unit sensing heat


Temperature Range:

0° to 40°C


Humidity Range:

15% to 95% Relative Humidity


Interconnect:

Up to 12 interconnected mains
powered easi-fit smoke or heat
alarms, along with an EI128 relay
base


Fixing:

Easi-Fit mounting base


Plastic material:

UL94VO flame retardant


Dimensions:

145mm diameter x 52mm depth


Weight:

281g


Warranty:

5 year (limited) warranty


Approvals:

Kitemarked to BS5446-2:2003, CE
Approved


Specifications are subject to change

Advertising