Precision Digital PD562 User Manual

Page 35

Advertising
background image

External AC

Power

(2) AC External Relay

CR Filter (snubber)
(Connect directly to the relay coil terminals)

Meter

R

!

CAUTION

!

CAUTION

Relay
(Verify relay coil ratings are less than the voltage and current ratings of the relay
contacts of the controller)

To prevent electric shock, be sure to turn off power to the Nova Controller and the source circuit
breaker before wiring.

7.12 Communication Wiring (RS-485)

!

CAUTION

„ Up to 31 slave controllers (Nova series controllers equipped with the RS-485 serial communication
option) can be connected.
„ Be sure to connect terminating resistors (220

Ω, 1/4 W) to slave and master controllers at

communication channel ends as shown above.

Master Station

NOVA Controller

Terminating Resistor

SHIELD

RTX+

RTX+

RTX+

RTX-

RTX-

RTX-

SG

SG

SG

Terminating Resistor

NOVA Controller

PD560 Series Nova Digital Process and Temperature Meter

Instruction Manual

35

Advertising
This manual is related to the following products: