Precision Digital PD570 User Manual

Page 20

Advertising
background image

SP

PV

Time Reset by

User

5-2-1-2 Operation of Limit Functions when O.ACT = FWD, HI.LO = HIGH, R.MD = OFF

Fig 4: Operation of Limit Functions with O.ACT set to FWD

HYS

The following illustration shows how each aspect of the limit control functions behave under over limit circumstances when
O.ACT is set to FWD operation.

1. Power supplied to t he controller. The limit control relay energizes.
2. The PV surpasses the SP. The OUT LED turns off. the OVER LED turns on. The latching limit control relay energizes.

The time begins being recorded.

3. The PV falls below the limit and hysteresis levels. The OVER LED turns off. The time count stops.
4. The PV surpasses the SP. The OVER LED turns on. The time count resets and begins again.
5. The PV falls below the limit and hysteresis levels. the OVER LED turns off. The time count stops.

When the r est button is pressed for 3 seconds, and the PV is below the SP, the OUT LED will turn on, and the limit control
relay will turn off.

OUT

LED

Limit

Control

Relay

OVER

LED

Time

Count

Power

to Unit

Reset

Pressed

ON

OFF

ON

OFF

ON

OFF

ON

OFF

2

3

4

5

Reset

Pressed

Reset

Pressed

(not accepted)

1

PD570 Series Nova Process and Temperature Limit Controller

Instruction Manual

20