Configuration – Riello UPS Sentinel Dual (Low Power) (1000 - 3000 VA) User Manual

Page 21

Advertising
background image

21

UPS

CONFIGURATION

The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for
individual requirements. It is possible to perform these operations using the UPStools software.

FUNCTION

DESCRIPTION

DEFAULT

POSSIBLE CONFIGURATIONS

• 50 Hz

Selects the nominal output
frequency

Output frequency

Auto

• 60 Hz

• Auto: automatic learning of the input frequency

Selects the nominal output
voltage

Output voltage

230V

220 - 240 in 1V steps

• ON LINE

Selects one of the 4
different operating modes

• ECO

Operating mode

ON LINE

• SMART ACTIVE

• STAND-BY OFF (MODE 1)

• Normal

Selects the mode of use of
the bypass line

Bypass operation

Normal

• Disabled with input/output synchronisation

• Disabled without input/output synchronisation

Automatic UPS power-off in
battery operation mode if
the charge is lower than 5%

Power-off due to

• Enabled

Disabled

minimum charge

• Disabled

Maximum battery operation
time

• Disabled (complete battery discharge)

Autonomy limit

Disabled

• (1 - 65000) sec. in 1 sec steps

Estimated autonomy time
remaining for the battery
low warning

Battery low

3 min.

(1 - 255) min. in 1 min steps

warning

Interval of time for the
automatic battery test

• Disabled

Battery test

40 hours

• (1 - 1000) h in 1 hour steps

Maximum charge

• Disabled

Selects the user overcharge
limit

Disabled

alarm threshold

• (0 - 103) % in 1% steps

Selects the permitted range
for the input frequency for
switching to the bypass and
for the synchronisation of
the output

Input frequency

± 5%

(±3 - ±10) % in 1% steps

tolerance range

* For configurations of the Fout = 50, 60Hz or if the sync is disabled with the input, the UPS downgrades the output power.