TROUBLESHOOTING

PROBLEM

POSSIBLE

CAUSE

PROCEDURE

The UPS does not

switch on

The UPS is switched

off

Check that the STAND-BY/ON switch is in the ON

position

The UPS input thermal

protection device has

been triggered

Disconnect non-essential equipment from the UPS.

Reset the protection (11) by depressing the button. If

the switch resets, start up the UPS and reconnect the

equipment one device at a time. If the protection

activates again, one of the connected devices is

causing an overload condition.

The UPS is working on

battery even though

mains power is

available

The UPS input

thermal protection

device has been

triggered

Disconnect non essential equipment from the UPS.

Reset the protection (11) by depressing the button.

The mains power

supply socket the UPS

is connected to is not

supplying power to the

device

Connect the UPS to another mains power supply

socket or have the mains supply checked by a

qualified electrician.

When there is a mains

power supply failure,

the UPS does not work

for the expected

runtime

The UPS battery is

not sufficiently

charged as there was

not enough time for it

to recharge after a

recent power failure

Wait for the battery to recharge. It recharges each time

the UPS is connected to a mains socket. It usually

takes 8 hours for the battery to recharge fully. UPS

operation time is a function of how charged the

battery is.

The battery needs to

be replaced.

Replace the battery.

The alarm icon (3) is lit

and the acoustic signal

sounds.

The UPS has a fault.

Remove the external devices from the UPS. Turn off

the UPS and disconnect it from the mains. Connect
the UPS to the mains and turn on again. If the UPS

message the anomaly again, contact your authorized

service centre.

Battery fault message.

Battery fault.

Replace the battery.

The UPS is not

communicating with a

PC.

The software sends a

message that

communication has

been lost.

Check that the USB cable is connected between the

UPS and the PC and that ‘USB’ has been selected as

the communication port in the software configuration.

The software is not

installed

Install the specific software for your computer’s

operating system.


TECHNICAL DATA

MODEL 600VA

800VA

INPUT

Voltage

230V +20%/ -25%

Frequency

50 or 60Hz +/-5% (with auto-sensing)

OUTPUT

Voltage (from battery)

230Vac +/-10% (Pseudo-sinusoidal wave)

Frequency (from battery)

50 or 60Hz +/-1Hz (with auto-sensing)

Trigger time

2-6 ms typical

Rated power VA

600

800

Rated power W

360

480

SURGE

SOCKETS

Max. current

5A

8A

PROTECTION

DEVICES AND

FILTERS

Overload and shortcircuit

protection

From mains: overload input protection.

From mains: automatic shutdown after 5 minutes with load

>110% and immediate shutdown with load >120% or for

shortcircuit.

From battery: automatic shutdown after 5 seconds with load

>110% and immediate shutdown with load >120% or for

shortcircuit.

BATTERY

Type

Sealed lead batteries, maintenance-free

Model

12V 7Ah

12V 9Ah

Typical recharge time

6-8 hours

Protection

Protection against total discharge, battery replacement

indicator

AMBIENT

CONDITIONS

Operating conditions

Max altitude 6,000 m, 0-90% non condensing humidity,

0-40°C

VARIOUS

Noise

<40dB (at 1m from source)

Earth leakage current

<1mA

RISOLUZIONE PROBLEMI

PROBLEMA

POSSIBILE

CAUSA

PROCEDURA

L’UPS non si accende.

L’UPS è spento.

Verificare che l’interruttore STAND-BY/ON sia in

posizione ON.

È scattata la protezione

d’ingresso dell’UPS.

Scollegare gli apparecchi non essenziali dall'UPS.

Ripristinare la protezione (11) premendo il relativo

pulsante fino al blocco. Accendere l'UPS e ricollegare

gli apparecchi uno alla volta. Se la protezione

interviene di nuovo, probabilmente uno degli

apparecchi collegati è la causa del sovraccarico.

L'UPS funziona da

batteria sebbene sia

disponibile la rete

elettrica.

È scattata la protezione

d’ingresso dell'UPS.

Scollegare gli apparecchi non essenziali dall'UPS.

Ripristinare la protezione (11) premendo il relativo

pulsante fino al blocco.

La presa di

alimentazione a cui è

collegato l’UPS non

fornisce alimentazione al

dispositivo.

Collegare l'UPS a un’altra presa di alimentazione o far

controllare l’impianto di rete da un elettricista

qualificato.

Quando si verifica un

guasto della rete

elettrica l'UPS non

funziona per il periodo

di tempo previsto.

La batteria dell'UPS non

è adeguatamente carica

in quanto non ha avuto il
tempo di ricaricarsi dopo

una recente mancanza

della rete elettrica.

Attendere che la batteria si ricarichi. La ricarica

avviene ogni qualvolta l'UPS è collegato a una presa di
alimentazione. In genere occorrono 8 ore per ricaricare

completamente la batteria. Il tempo di funzionamento

dell'UPS da batteria è ridotto finché la batteria non è

completamente carica.

La batteria è da

sostituire.

Sostituire la batteria.

Il simbolo di allarme

(3) si accende e il

segnale acustico è

attivo.

L’UPS ha rilevato

un’anomalia.

Scollegare gli apparecchi dall’UPS. Spegnere l’UPS e

togliere l’alimentazione. Alimentare l’UPS e

riaccenderlo nuovamente. Se la segnalazione si

ripresenta rivolgersi al vostro centro di assistenza

autorizzato.

Si attiva la

segnalazione di
batteria guasta.

Batteria guasta.

Sostituire la batteria.

L’UPS non comunica

con il pc.

Il software manda un

messaggio di

comunicazione persa.

Controllare che il cavo USB sia collegato all’Ups e al

pc e che nella configurazione del software di

comunicazione sia selezionata USB come porta di

comunicazione.

Il software non è

installato

Installare il software specifico per il sistema operativo

del vostro pc.




DATI TECNICI

MODELLO 600VA

800VA

INGRESSO

Tensione

230V +20%/ -25%

Frequenza

50 or 60Hz +/-5% (con autoapprendimento)

USCITA

Tensione (da batteria)

230Vac +/-10% (Onda pseudo sinusoidale)

Frequenza (da batteria)

50 or 60Hz +/-1Hz (con autoapprendimento)

Tempo di intervento

Tipico 2-6 ms

Potenza nominale VA

600

800

Potenza nominale W

360

480

PRESE SURGE

Corrente max.

5A

8A

PROTEZIONE

Protezione sovraccarico e

cortocircuito

Da Rete: protezione d’ingresso per sovraccarico.

Da Rete: spegnimento automatico dopo 5 minuti con carico

>110% e immediato con carico >120% o con cortocircuito.

Da Batteria: spegnimento automatico dopo 5 secondi con

sovraccarico >110% ed immediato con sovraccarico >120% o

con cortocircuito.

BATTERIA

Tipo

Sigillate, al piombo, senza manutenzione

Modello

12V 7Ah

12V 9Ah

Tempo di ricarica tipico

6-8 ore

Protezioni

Protezione contro la scarica totale, indicatore di sostituzione

batteria

CONDIZIONI

AMBIENTALI

Condizioni operative

Altitudine max 6,000 m, 0-90% di umidità non condensata, 0-

40°C

VARIE

Rumorosità

<40dB (a 1 m dalla sorgente )

Correnti di dispersione

verso terra

<1mA


Thank you for choosing our product.


IMPORTANT SAFETY NOTES

This device can be installed by anyone, provided that they READ THIS MANUAL CAREFULLY
AND FOLLOW THE INSTRUCTIONS WITHIN IT.
This manual contains detailed instructions for the use and installation of the UPS.
This manual should be kept close to the UPS and READ BEFORE THE UPS IS INSTALLED
AND USED

© No part of this manual may be reproduced, even partially, without the manufacturer’s
authorisation. For purposes of improvements the manufacturer reserves the right to change
specifications at any time and without notice.


Warning:
Read the following instructions carefully and keep this manual handy for easy referral.
The mains power supply socket used to power the UPS must have an earth connection.
Potentially dangerous electrical voltages are generated inside this device, even when the UPS is
switched off. All repairs must be carried out by authorised personnel only.
Voltage may be present on the UPS output sockets even when the UPS is not connected to a mains
power supply.
In the event of a mains power supply failure (emergency UPS operation), do not unplug the power
supply cable to the UPS, to ensure earth continuity to the connected loads.
Do not allow liquids and/or other foreign bodies to enter the UPS.
Since the mains power supply cable acts as a separation device, the mains power supply socket
used that connects to the rear of the UPS must be accessible and easy to disconnect.
In dangerous conditions and/or to disconnect the UPS from sources of energy, (whether mains or
batteries), disconnect the power supply cable from the mains socket or from the back of the UPS
and shut down the UPS using the STAND-BY/ON switch (6).
Risk of electric shock. Since internal components are connected to the batteries, they will remain
powered, and therefore dangerous, even after the device has been disconnected from a mains power
supply. Disconnect the batteries and ensure no voltage is present before carrying out any repair or
maintenance operations.
The UPS generates an earth leakage current. Ensure that the sum of the UPS and load earth leakage
current is less than 3.5mA.
Replaced batteries should be considered as TOXIC WASTE and treated as such.
Do not throw the batteries into a fire.
Do not try to open the batteries: they do not require any maintenance. Furthermore the electrolyte is
dangerous if it comes into contact with skin or eyes and may be toxic.
The batteries can cause electric shock and have a high short circuit current. Take the necessary
safety measures and precautions when handling them:

- do not wear watches, rings, necklaces or any other metallic material
- only use tools with insulated handles

Only use the UPS following the specific instructions in this user manual.



DESCRIPTION OF THE UPS

Front and rear views:

1.

Back-up sockets (local type)

2.

Surge sockets (local type)

3.

/RED LED: various messages (see the “Alarms and Report Signals table”)

4.

/YELLOW LED: the UPS operates on battery

5.

/GREEN LED: the UPS operates from the mains power supply

6.

Main STAND-BY/ON switch

7.

Battery compartment locking screws

8.

Battery compartment

9.

Back-up sockets (IEC type)

10.

USB port

11.

Input protection device

12.

Power supply cable



INSTALLATION

Opening of packing and verification of its contents
Remove the UPS from its packaging and check that there is no visible damage caused during
shipping. If there is any noticeable damage to the UPS, pack the product up and return to
where it was purchased.

Packing contents

¾

UPS

¾

User manual

¾

Warranty card


Positioning

Follow the instructions below to correctly install and position the UPS:

¾

The UPS must be placed on a horizontal surface.

¾

The UPS must not be exposed to direct sunlight.

¾

Ensure that the ambient temperature is between 0°C and 40°C, for optimal performance use
at a maximum temperature of 25°C.

¾

The ambient humidity is less than 90%.

¾

Avoid dusty environments.

¾

Place the UPS at least 5cm from a wall to ensure adequate ventilation.

¾

Ensure that the UPS or any other heavy object is clear of the power supply cable.

¾

Ensure that the cables connecting loads to the UPS are not longer than 10metres.


Storage

The UPS must be fully recharged if it is to be stored for a long time. A full discharge and charge
cycle should be carried out every 6 months to keep the battery in good condition.

OPERATION

Connection to mains and battery charging

Please ensure that the mains power supply to be used with this UPS has upstream protection rated
at either 10A.
¾

Connecting the UPS to the mains with the power supply cable provided.

¾

The UPS will recharge its battery each time it is connected to a mains power supply (even if
it is powered down). We recommend that the UPS is charged for 6-8 hours before connecting
the loads.



Connecting the loads
After having loaded the UPS, loads can be connected (e.g.: computer, monitor, etc.) to the output
sockets, according to the following indications:

¾

Back-up sockets (1) (9): these sockets are only powered when the UPS is on. Should mains
power fail, the back-up sockets are battery-powered.

N.B.: we recommend not running laser printers or laser print devices from back-up sockets
(1) (9) together with other computer peripheral equipment. On odd occasions, this equipment
uses a greater quantity of energy than when at rest. This set-up may lead to UPS overload and
cause all equipment connected to be switched off.

¾

Surge sockets (2): additional filtered sockets limiting line surge and mains disturbances.
They do not protect the load from power failures or short blackouts. They can be used to
power non-essential devices such as, for example, printers, scanners and suchlike. Small
laser printer devices can be installed on these sockets.

N.B.: the sockets are also powered when the UPS is in stand-by.



Starting up/Shutting down

Press the main STAND-BY/ON switch to start-up the UPS and power the loads.
Press the switch again to shut down the UPS and power down from the loads.



Starting up on battery (Cold start)

If there is no mains power supply present, pressing the main power switch will cause the UPS to
start up using its battery as a source of power.
Warning: when starting up on battery, the output frequency is set to 50Hz.



USB port

The UPS can be connected to a computer for remote monitoring and shutdown operations using a
USB cable. The UPS management software and related manual can be downloaded from
www.riello-ups.com.



Replacing the batteries

CAUTION: The models require replacement by qualified service personnel.
Contact technical support for information concerning the exact model of battery to use.

- Shut down the UPS and disconnect the power cable. Remove the screws that hold the battery

compartment in place under the UPS. (Fig. A)


- After removing the cover, carefully remove the battery from its housing. (Fig. B)

- Disconnect the two wires from the battery (simply by pulling them). Replace the battery with

another of the same type, taking care to respect the polarity. Re-assemble the compartment. (Fig.
C)



ALARMS AND REPORT SIGNALS

Description

Switch

position

(6)

Led functioning

Other report signals

Green led

Yellow led

Red led

Stand-by STAND-BY

Blinking

Operation on mains

power

ON Steady

Operation on battery

ON

Blinking

Slow blinking acoustic

signal

End of discharge

warning

ON

Blinking

Blinking acoustic signal

Overload

ON

Blinking

Blinking acoustic signal

Battery fault

ON

Steady

Steady

Blinking acoustic signal

Alarm or fault (other

than overload)

ON

Steady

Continuous acoustic

signal

Vi ringraziamo per la scelta del nostro prodotto!


NOTE IMPORTANTI PER LA SICUREZZA

Questa apparecchiatura può essere installata da qualsiasi persona, previa ATTENTA E
SCRUPOLOSA LETTURA DEL PRESENTE MANUALE.
Questo manuale contiene le istruzioni dettagliate per l’uso e l’installazione dell’UPS.
Per informazioni sull’utilizzo e per ottenere il massimo delle prestazioni dalla Vostra
apparecchiatura, il presente manuale dovrà essere conservato con cura vicino all’UPS e
CONSULTATO PRIMA DI OPERARE SULLO STESSO.

© E’ vietata la riproduzione di qualsiasi parte del presente manuale anche se parziale salvo
autorizzazione della ditta costruttrice. Per scopi migliorativi, il costruttore si riserva la facoltà di
modificare il prodotto descritto in qualsiasi momento e senza preavviso.

Attenzione:

Leggere con cura le seguenti istruzioni e tenere a disposizione questo manuale per una rapida
consultazione.
La presa di rete cui l’UPS è collegato deve essere dotata di connessione di terra.
All’interno di questa apparecchiatura vi sono tensioni potenzialmente pericolose, anche con UPS
spento. Tutte le riparazioni dovranno essere effettuate esclusivamente da personale autorizzato.
Le prese di uscita dell’UPS potrebbero essere in tensione anche quando l’UPS non è collegato alla
rete.
In caso di mancanza di rete (funzionamento dell’UPS da batteria), non staccare il cavo di
alimentazione per garantire la continuità di terra all’utenza collegata.
Evitare che liquidi e/o altri corpi entrino nell’UPS.
Poiché il cavo di alimentazione separabile è inteso come dispositivo di sezionamento, la presa di
rete cui l’UPS è collegato e/o il retro dell’UPS devono essere accessibili e facilmente scollegabili.
In condizioni di pericolo e/o per scollegare l’UPS dalle sorgenti di energia, rete e batterie,
sconnettere il cavo di alimentazione dalla presa di rete o dal retro dell’UPS e spegnere tramite
l’interruttore STAND-BY/ON (6).
Rischio di scossa elettrica. Anche dopo aver scollegato l’apparecchiatura dalla rete elettrica di
alimentazione, i componenti interni dell’UPS essendo collegati alle batterie, sono ancora in
tensione, quindi pericolosi. Prima di effettuare qualsiasi tipo di riparazione o manutenzione,
scollegare le batterie e verificare che non sia presente tensione.
L’UPS genera una corrente di dispersione. Assicurarsi che la somma della corrente di dispersione
verso terra dell’UPS e del carico connesso sia inferiore del limite di 3,5mA.
Le batterie sostituite vanno considerate RIFIUTO TOSSICO e trattate di conseguenza.
Non gettare le batterie sul fuoco.
Non tentare di aprire le batterie: sono prive di manutenzione. Il liquido elettrolita è pericoloso per la
pelle e per gli occhi, e può risultare tossico.
Le batterie possono essere causa di scossa elettrica e sono dotate di un alta corrente di cortocircuito.
Prendere le necessarie precauzioni e misure di sicurezza, di seguito elencate, quando si maneggiano
delle batterie:

- non indossare orologi, anelli, catenine o qualsiasi altro materiale metallico
- usare solo attrezzi con impugnatura isolata

Usare l’UPS seguendo le specifiche previste secondo quanto prescritto dal presente manuale d’uso.


DESCRIZIONE DELL’UPS

Viste frontali e posteriori:

1.

Prese di backup (tipo locale)

2.

Prese Surge (tipo locale)

3.

/LED ROSSO: segnalazioni varie (vedi tabella “Allarmi e segnalazioni”)

4.

/LED GIALLO: UPS in funzionamento da batteria

5.

/LED VERDE: UPS acceso con rete presente

6.

Interruttore principale STAND-BY/ON

7.

Vite bloccaggio vano batteria

8.

Vano batteria

9.

Prese di backup tipo IEC

10.

Porta USB

11.

Protezione di ingresso

12.

Cavo di alimentazione


INSTALLAZIONE

Apertura dell’imballo e verifica del suo contenuto

Rimuovere l’UPS dall’imballo e verificare che non vi siano danni visibili causati durante il
trasporto. Qualora si notassero danni all’UPS reimballare il prodotto e restituire presso il centro di
acquisto.


Contenuto dell’imballo

¾

UPS

¾

Manuale d’uso

¾

Cartolina Garanzia


Collocazione

Seguire le seguenti indicazioni per installare e posizionare correttamente l’UPS:
¾

L’UPS deve essere posto su di un piano orizzontale

¾

L’UPS non deve essere esposto alla luce diretta del sole

¾

Assicurarsi che la temperatura dell’ambiente sia compresa tra 0°C e 40°C, per un
funzionamento ottimale utilizzare a una temperatura massima di 25°C.

¾

Il tasso di umidità dell’ambiente deve essere inferiore al 90%

¾

Evitare ambienti polverosi

¾

Posizionare l’UPS almeno a 5 cm di distanza dai muri circostanti al fine di permettere
un’adeguata aerazione

¾

Assicurarsi che ne l’UPS ne qualche altro oggetto pesante schiacci il cavo di alimentazione

¾

Il cavo che connette i carichi all’UPS non deve superare i 10 metri di lunghezza


Immagazzinamento

È necessario ricaricare completamente l’UPS se necessita di un lungo periodo di
immagazzinamento. Ogni 6 mesi effettuare un ciclo di scarica e carica completa per conservare in
buono stato la batteria.

FUNZIONAMENTO


Collegamento alla rete e carica delle batterie

Verificare che nell’impianto a monte dell’UPS vi sia una protezione da sovracorrenti. Il valore della
protezione consigliata è di 10A.
¾

collegare l’UPS alla rete elettrica tramite il cavo di alimentazione fornito in dotazione.

¾

L’UPS effettua la ricarica della batteria ogni qualvolta viene collegato all’alimentazione di
rete (anche se spento). Caricare per 6-8 ore l’UPS prima di collegare i vari carichi.


Connessione dei carichi

Dopo aver caricato l’UPS è possibile collegare i diversi carichi (es: computer, monitor, ecc…) alle
prese presenti sull’UPS.
¾

Prese Backup (1)(9):queste prese sono alimentate solo quando l’UPS è acceso. In caso di
mancanza rete le prese di backup sono alimentate tramite batteria.
Nota: si consiglia di non applicare stampanti laser o dispositivi di stampa a laser sulle prese
di backup (1)(9) assieme ad altre periferiche del computer. Queste apparecchiature assorbono
occasionalmente una quantità maggiore di energia rispetto a quando sono a riposo. Questa
configurazione potrebbe portare in sovraccarico l’UPS e allo spegnimento di tutte le
apparecchiature collegate.

¾

Prese Surge (2): prese addizionali filtrate, limitano le sovratensioni e disturbi di rete; non
proteggono il carico dagli eventi di mancanza rete o brevi interruzioni.
Possono essere
utilizzate per alimentare dispositivi non essenziali quali ad esempio stampanti, scanner o
altro. Su queste prese è possibile installare piccoli dispositivi di stampa a laser.

Nota: le prese sono alimentate anche quando l’UPS è in stand-by.


Accensione/Spegnimento

Premere l’interruttore principale STAND-BY/ON per accendere l’UPS ed alimentare i carichi.
Per spegnere l’UPS e togliere l’alimentazione ai carichi premere nuovamente l’interruttore
principale.


Accensione da batteria (Cold start)

In caso di assenza di rete, premendo l’interruttore principale, l’UPS effettua l’accensione da
batteria.

Attenzione: quando viene effettuata l’accensione da batteria la frequenza di uscita è impostata

a 50Hz.


Porta USB

L’UPS può essere collegato tramite un cavo di collegamento USB ad un computer per funzioni di
monitoraggio e shutdown del sistema operativo. È possibile scaricare il software di gestione ed il
relativo manuale dal sito internet www.riello-ups.com.



Sostituzione della batteria

ATTENZIONE:La sostituzione delle batterie deve essere effettuata esclusivamente da personale qualificato.
Contattare l'assistenza tecnica per informazioni relative al modello esatto di batteria da utilizzare.

- Spegnere l’UPS e scollegare il cavo di alimentazione. Rimuovere le viti che fissano il vano

batterie situate sotto L’UPS (Fig. A)


- Dopo aver rimosso il coperchio, rimuovere con delicatezza la batteria dal proprio alloggiamento

(Fig. B)


- Scollegare quindi i due fili dalla batteria (semplicemente tirandoli). Sostituire la batteria con una

dello stesso tipo facendo molta attenzione a rispettare la polarità. Riassemblare il tutto (Fig. C)



ALLARMI E SEGNALAZIONI


Descrizione

Posizione

interruttore

(6)

Funzionamento Led

Altre segnalazioni

Led Verde

Led Giallo

Led Rosso

Stand-by STAND-BY

Intermittente

Funzionamento

da rete

ON Fisso

Funzionamento

da batteria

ON

Intermittente

Segnale acustico

intermittente lento

Preavviso di fine

scarica

ON

Intermittente

Segnale acustico

intermittente

Sovraccarico ON

Intermittente

Segnale acustico

intermittenti

Batteria guasta

ON

Fisso

Fisso

Segnale acustico

intermittente

Allarme o blocco

(diverso dal

sovraccarico)

ON

Fisso

Segnale

acustico

continuo

Advertising