Emerson 650VA User Manual

Liebert, Ups c, Caution

Advertising
background image

Liebert

®

PSA

Quick-Start Guide - 500VA/650VA, 120V

I

MPORTANT

S

AFETY

I

NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during
installation and maintenance of the UPS.
• Intended for installation in a controlled environment.
• Maximum ambient temperature 104°F (40°C).

• Do not connect equipment that may overload the UPS or demand half-wave

rectification, such as a laser printer.

• Connect the UPS only to an earthed / grounded outlet that meets national and local

electrical safety guidelines.

• Locate the UPS near a wall outlet. Do not use an extension cord between the UPS and

the outlet.

• The Liebert PSA has been designed for small office/home office use only; it is NOT

recommended for use in life-support applications.

• In the event of an emergency, press the OFF button and disconnect the power cord

from the AC power supply to properly disable the UPS.

• Do not attach power strips or surge suppressors to the UPS.
• Do not attempt to service any parts inside the UPS except the batteries. Failure to adhere

to this could cause personal injury or equipment malfunction and void the warranty.

• For technical support:

• Visit

www.liebert.com

or

• Send an e-mail to

[email protected]

.

S

ETUP

UPS C

ONTROLS

AND

C

ONNECTIONS

!

CAUTION

To reduce the risk of fire, connect only to a circuit provided with
20 amperes maximum branch circuit overcurrent protection in
accordance with the national code, ANSI/NFPA 70.

Step 1 Inspect the Package

Inspect the package and the UPS upon receipt. Notify the carrier and dealer of visible
damage.

Step 2 Decide Where to Place the UPS

The UPS must be placed indoors, protected from water, direct
sunlight and excessive heat.

Provide at least 4" (100mm) of clearance on all sides of the unit
for proper ventilation.

Step 3 Charge the UPS Battery Before

Use

The UPS battery is not charged before shipping. It MUST be charged before use.

• Connect the UPS power cord to a wall outlet and charge for at least eight hours.

Note: If battery is placed in storage, charge the battery every six months if kept at
5°F to 85°F (-15°C to 29°C)—or every three months if kept at 86°F (30°C) or higher.

Step 4 Start the UPS

After the battery is fully charged:

• Turn on the UPS by pressing the On/Off button (see Figure 1 below).

LED 1 should be illuminated (green), indicating the UPS is operating in Normal Mode.

Step 5 Check the Site Wiring Fault Indicator

See figure at right for the location of the Site Wiring Indicator on the rear of
the UPS.

• Check the rear of the UPS to make sure the Site Wiring Fault indicator is

NOT illuminated.

Caution: If the Site Wiring Fault indicator is illuminated, have a qualified
electrician check the wall receptacle wiring and fix any problems.

Step 6 Connect the Loads

The UPS has three battery backup outlets that
provide power when the UPS operates on bat-
tery (see Figure 2 below).

• Plug the loads into the battery backup outlets

on the rear of the UPS.

Caution: Do not connect a laser printer to the
UPS.

Step 7 Connect the Network Surge Protection

The UPS has two RJ-45 jacks for network lines (see
Figure 2 below).

• Connect a single-line network cable into the RJ-45

network surge protection IN jack on the rear of the
UPS.

• Connect an RJ-45 cable from the OUT jack on the

rear of the UPS to a port on a PC or network device
such as a router.

Step 8 Set Up Liebert shutdown software

To start using the Liebert shutdown software:

• Install the Liebert shutdown software. See the software

user manual for installation instructions.

• Connect one end of the USB cable (supplied) to the USB

port on the rear of the UPS. Connect the other end to a
USB port on the computer. See the software user manual
for operating instructions.

UPS

USB

cable

Liebert

shutdown

software

CD

Quick-start

guide

!

EMERSON

Network Power

Liebert

®

PSA

AC Power System

UPS Status, Alarm Conditions and Alerts

Condition

LED

Color

Solid/Flashing

Audible Alarm

Normal Mode

LED 1

Green

Solid (steady glow)

(None)

Battery Mode

LED 1

Green

Flashes every 3 seconds

Every 3 seconds

Battery Low

LED 1

Green

Flashes every 1 second till end of discharge (EOD)

Every 1 second

Overload

LED 2

Amber

Solid (steady glow) until load drops or breaker trips

Continuous

Battery Replacement

LED 2

Red

Flashes every 1 second for 5 seconds only

Every 1 second for 5 seconds only

Fault

LED 2

Red

Solid (steady glow) until UPS shuts down after 5 seconds

Continuous until UPS shuts down

LED 2 (red = fault;

amber = overload)

Fault

symbol

Overload

symbol

Utility

symbol

On/Off button

LED 1

(green)

Battery backup

outlets (3)

NEMA 5-15R

RJ-45 jacks (2) -

network protection

NEMA

5-15P

USB

interface

Surge outlet (1)

NEMA 5-15R

Input

breaker

Site Wiring

Fault indicator

Figure 2 - Rear Panel

Figure 1 - Front Panel LEDs