Amprobe VPC-10 Voltage-Continuity-Tester User Manual

Amprobe Measuring instruments

Advertising
background image

Voltage and Continuity Tester

Model VPC-10

Instruction Manual

m

Safety Information

• Never use the tester if it or its test leads appear damaged

• Never apply more than 600V DC or 600V AC RMS between any terminal

and earth ground.

(

If the LED turns on it indicates the presence of voltage at the probe tip.

• When using the probes, do not touch the metal probe tips.

• Disconnect the live test lead before disconnecting the common test lead.

• Before each use, verify the tester’s operation by measuring a known voltage.

Automatic Operation

The tester automatically turns on when you place the probes across a complete circuit.

The tester selects continuity or dc or ac voltage mode based on the resistance or volt-

age between the probes. The tester automatically turns off when you remove the

probes from the complete circuit.
Measuring Voltage

Connect test leads across the source or load under measurement, the LEDs turn on at

between 70% and 100% of their rated voltages.

Testing for Continuity

Turn off circuit power before testing

Beeper indicates shorts lasting 1ms or longer

OPEN

SHORT or 0-85 KΩ

Specifications
Function

Range

Accuracy

AC voltage(V)

24,120,208,240,277,480,600

-30% to 0% of reading

DC voltage(V)

6,12,24,36,48,110,220

-30% to 0% of reading

Continuity test: Audible threshold 0-85kΩ, Continuity beeper 2KHz

Maximum Voltage Between any Terminal and Earth Ground:

600 V Overvoltage Category III

Input Impedance: 1MΩ

Temperature: Operating: 5˚C (41˚F) to 40˚C (104˚F)

Storage : -30°C to +60°C
Altitude: Operating: 2000m; Storage:10,000m
Relative Humidity:

80% for Temp up to 31˚C decreasing linearly to 50% RH at 40˚C

Battery Type and Life: AA(2); 350 hours with NEDA 15˚F or IEC R6

Safety: Complies with EN61010-1:1993 for use in overvoltage CAT III environments

Pollution Degree: 2

For indoor use only

EMC Regulations: EN50081-1, EN50082-1

DC Voltage

600V DC maximum

600

AC Voltage

600V RMS maximum

45Hz to 66Hz

Continuity

Continuity

r

Beeping

220V AC