5.2.3 Configuration by Controller Application

The second option to configure the ILX69-

PBS is through the controller application. If you’re

unable to install the AOP due to company policy or other reasons, you will need to manually
configure the module through the controller application.

The "Force User Config" parameter in this array must be set to 1. With this method, the
ILX69-PBS will not start any network communication unless the master and ILX69-PBS
configuration match. The following table outlines the mapping of the configuration data
image.

Word
Offset

Configuration
word

Data
type

Low/High
Byte

Description

Valid values

0

Local:1:C.Data[0]

INT

LOW Byte

Reconfiguration Event 0


Reserved, set to 0

HIGH Byte

Reconfiguration Event 1

1

Local:1:C.Data[1]

INT

LOW Byte

Reconfiguration Event 2


Reserved, set to 0

HIGH Byte

Reconfiguration Event 3

2

Local:1:C.Data[2]

INT

LOW Byte

Bus Address

0 to 125
0 = ForceMasterConfig
1 = ForceUserConfig

HIGH Byte

Force User Configuration

3

Local:1:C.Data[3]

INT

Reserved

4

Local:1:C.Data[4]

INT

Watchdog Time

0 to FFFFh

5

Local:1:C.Data[5]

INT

Number of valid config bytes
(starting with Local:1:C.Data[8])

2 to 48

6

Local:1:C.Data[6]

INT

Reserved

7

Local:1:C.Data[7]

INT

Reserved

8

Local:1:C.Data[8]

INT

LOW Byte

Module 1 Type

HIGH Byte

Module 1 Length

9

Local:1:C.Data[9]

INT

LOW Byte

Module 2 Type

HIGH Byte

Module 2 Length

...

...

...

...

31

Local:1:C.Data[31]

INT

LOW Byte

Module 24 Type

HIGH Byte

Module 24 Length

32

Local:1:C.Data[32]

BOOL -

IP Config flags 1, Static or
Dynamic

0 or 1

33

Local:1:C.Data[33]

BOOL -

IP Config flags 2, Static or
Dynamic

0 or 1

34

Local:1:C.Data[34]

INT

-

IP Configuration

0 = BOOTP
1 = DHCP
2 = FIXED IP

35

Local:1:C.Data[35]

SINT

LOW Byte

IP Address

00.00.00.00 through
FF.FF.FF.FF


HIGH Byte

Advertising