Diagnostics and Troubleshooting

MVI69-HART ♦ CompactLogix Platform

User Manual

HART Multi-drop Master Communication Module

Page 78 of 169

ProSoft Technology, Inc.

March 29, 2012

To begin the display of the communications data, you will then want to press [B]

to tell the module to start printing the communications traffic out on the debug

port of the module. After you have pressed [B],

you should see something like

the following:

The <R+> means that the module is transitioning the communications line to a

transmit state.
All characters shown in <> brackets are characters being sent out by the module.
The <R-> shows when the module is done transmitting data, and is now ready to

receive information back.
And finally, all characters shown in the [ ] brackets is information being received

from another device by the module.
After taking a minute or two of traffic capture, you will now want to stop the "Data

Analyzer". To do so, press the [S] key, and you will then see the scrolling of the

data stop.
When you have captured the data you want to save, open the Transfer menu and

choose Capture Text. On the secondary menu, choose Stop.

You have now captured, and saved the file to your PC. This file can now be used

in analyzing the communications traffic on the line, and assist in determining

communication errors.