ProSoft Technology MVI69-103M User Manual

Page 77

Advertising
background image

Reference MVI69-103M

♦ CompactLogix or MicroLogix Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 77 of 131

November 3, 2008

Data Type

Address Type

Length

Example

9 Word 5

words

Address 100 refers to 9 consecutive words starting
at word 100.

20 Bit

2

bits

Address 160 refers to the first and second bits
from word 10.

Therefore, address 16000 represents bit zero in word 1000 of the module's
database. Short floating-point, 32-bit strings and integrated total values each
occupy a double-word space in the database. Therefore, short float database
address of 100 represents the two words, 200 and 201, in the modules database.
Identification objects are stored as byte values in the modules database.
Identification object address 1000 is stored in the module's database in word
addresses 500 to 505.

When setting the monitored data and commands, each point is defined by its
ASDU type, function code, and information number. Valid function codes are
listed in the following table.

Function Code

Symbol

Number

Distance Protection

T(z)

128

Over-current Protection

I>>

160

Transformer Differential
Protection

rIt 176

Line Differential Protection

rIl

192

Global Function Type

GLB

255

Refer to Protocol Interoperability Documentation for a full listing of the protocol
support offered by the module.

As blocks are transferred between the module and the processor, each block
contains block identification codes that define the content or function of the block
of data transferred. The block identification codes used by the module are
displayed in the following table.

Block Range

Descriptions

-1 Null

block

0 Null

block

1 to 20

Read or write data

9901

User Constructed Command

9902

Command Control Block (Add command to Command List Queue)

9903

Event Messages from Master port

9950

Command List Error data

9970

Set PLC time using module's time

9971

Set module's time using CompactLogix or MicroLogix time

9998

Warm Boot Request from CompactLogix or MicroLogix (Block contains no
data)

9999

Cold Boot Request from CompactLogix or MicroLogix (Block contains no
data)