The following table defines the contents of the Configuration Error (Cfg Err) word.
Each bit in the word corresponds to an error condition recognized when the
module is configured. There is a separate word for each application port. This
data is reported in the status data area previously defined.

Bit

Code

Description

0

0x0001

Invalid baud rate selected

1

0x0002

Invalid parity selected

2

0x0004

Received timeout set to 0

3

0x0008

Invalid Port selected for a session

4

0x0010

Invalid sector count for session

5

0x0020

Could not allocate memory for sector of a session.

6

0x0040

7

0x0080

Invalid failure delay or confirm timeout for session.

8

0x0100

9

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

The following table lists all potential errors that can be generated by the IEC
60870-5-103 Master driver:

5.6.2 MVI56-IEC 60870-5-103 Master Communication Module Error

Codes

Error

Description

51

Physical layer error - Error transmitting message

52

Physical layer error - Intercharacter timeout occurred before message fully received.

53

Physical layer error - Frame not entirely received before timeout condition.

54

Physical layer error - Invalid frame length.

101

Link layer error - Invalid checksum received

102

Link layer error - Address unknown to module

103

Link layer error - Link established

104

Link layer error - Link failed

105

Link layer error - Received primary

106

Link layer error - FCB error discard

107

Link layer error - FCB error repeat

108

Link layer error - Invalid start character received

109

Link layer error - Invalid second character received

110

Link layer error - Invalid ending character received

111

Link layer error - Length mismatch error

112

Link layer error - Illegal function

113

Link layer error - No confirmation received