ProSoft Technology MVI56-101S User Manual

Page 41

Advertising
background image

MVI56-101S ♦ ControlLogix Platform

Configuring the MVI56-101S Module

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 41 of 193

August 2, 2011

2.3.15 Maximum ASDU Resp Len

25 to 252

Sets the maximum ASDU response message length (usually 252).

2.3.16 Cause of Trans(mission) Octets

1 or 2

Specifies the number of COT octets (1 or 2)

2.3.17 Freeze Start Type

D

=

D

AY

,

H

=

H

OUR

,

M

=

M

INUTE

,

N

=

N

OT USED

The Freeze Start Type parameter defines when the module starts sending the
M_IT messages.

Example I - Freeze Start Type
If the module should send the counter points on the hourly turn around time and
also 45 minutes later, the Mode A parameters should be configured as follows:

So the module would send events as follows (Hours:Minutes:Seconds):

17:00:00

17:45:00

18:00:00

18:45:00

19:00:00

19:45:00