Rs-232 configuration/debug port, Rs-232, Configuration/debug port – ProSoft Technology MVI56-PDPS User Manual

Page 68

Advertising
background image

MVI56-PDPS ♦ ControlLogix Platform

Reference

Profibus DP Slave Communication Module

Page 68 of 88

ProSoft Technology, Inc.

April 22, 2008

Bit

Designation

Significance

4

Unsync

The 'Unsync' command cancels the 'Sync' command.

5

Sync

The ASCI output data transferred with a WRITE_READ_DATA
telegram is changed from data transfer buffer next state buffer.
The following transferred output data is kept in data transfer buffer
until the next 'Sync' command is given.

6,7

Reserved

The Reserved designation specifies that these bits are reserved
for future function expansions.

5.3

RS-232 Configuration/Debug Port

This port is physically an RJ45 connection. An RJ45 to DB-9 adapter cable is
included with the module. This port permits a PC based terminal emulation
program to view configuration and status data in the module and to control the
module. The cable for communications on this port is shown in the following
diagram:

5.3.1 Disabling the RSLinx Driver for the Com Port on the PC

The communication port driver in RSLinx can occasionally prevent other
applications from using the PC's COM port. If you are not able to connect to the
module's configuration/debug port using ProSoft Configuration Builder (PCB),
HyperTerminal or another terminal emulator, follow these steps to disable the
RSLinx Driver.

1

Open RSLinx and go to Communications>RSWho

Advertising
This manual is related to the following products: