2.2.6 Port[x].StopBits

1 or 2

Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to re-synchronize,
use two stop bits.

All devices communicating through this port must use the same number of stop
bits.

2.2.7 Port[x].RTSOn

0 to 65535

milliseconds

This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.

2.2.8 Port[x].RTSOff

0 to 65535 milliseconds

This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.

2.2.9 Port[x].Handshaking

Handshaking is a negotiation process between devices that establishes a data
connection. Select the handshaking type that best matches the needs of the
devices connected to the port.

Value

Description

0

No hardware or software handshaking

1

RTS/CTS hardware handshaking

2

DTR/DSR hardware handshaking

3

XON/XOFF software handshaking

2.2.10 Port[x].RTermCnt

0 to 12 characters

This parameter specifies the number of termination characters that define the
end of a received message. Use this parameter if you set the P

ORT

[X].T

YPE

Port[x].Type (page 54) value to 1, 3, 5, 7, 9, 11, 13 or 15.

2.2.11 Port[x].RTermChar

This array of up to 12 characters specifies the termination characters that define
the end of a received message. Each character occupies one position in the
array. The number of termination characters you enter here must match the
value in the P

ORT

[X].RT

ERM

C

NT

tag.