ProSoft Technology MVI56-GEC User Manual

Page 48

Advertising
background image

Ladder Logic

MVI56-GEC ♦ ControlLogix Platform

User Manual

Generic ASCII Ethernet Communication Module

Page 48 of 108

ProSoft Technology, Inc.

October 8, 2010

3.1.16 CfgErrword (Configuration/Error Status Flags)

The CfgErrword member reports configuration errors for the respective server. If

the module is not functioning as expected, inspect the value presented in this

object. If a configuration error exists, the associated bit will be set. A value of

zero for the bit indicates the configuration value is valid. This does not guarantee

that the module is configured correctly for your application. The bits used by this

member are shown below:

Bit Position

Description

Bit 0

0x01

A value other than Yes or No was entered for the enabled

parameter.

Bit 1

0x02

Not used.

Bit 2

0x04

A value less than 5000 but not 0 is entered for the timeout

parameter.

Bit 3

0x08

An invalid value is entered for the Connection Close Type

parameter. The program only accepts a value of 0 to 2.

Advertising