Module Configuration and Installation

3170-MBS ♦ Flex Platform

User Manual

Modbus Slave Interface Module

Page 16 of 55

ProSoft Technology, Inc.

October 27, 2010

3.3

Wiring

Attention: When connecting wiring, torque terminal screws to 7 to 9 inch-pounds.

Connect

To

TxRxD-

1

TxRxD+

2

1 Connect the Modbus cable to the removable connector.
2 Connect +24V dc input to the left side of the lower connector, terminal E.
3 Connect 24V common to the left side of the upper connector, terminal D.
4 Connections G and F are used to pass 24V dc power (G) and 24V common

(F) to the next module in the series (if required).

3.3.1 RS-485 Tip

If communication in the RS-485 mode does not work at first, despite all attempts,

try switching termination polarities. Some manufacturers interpret + and -, or A

and B, polarities differently.