Configuration as a Modbus Slave

MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 62 of 199

ProSoft Technology, Inc.

June 18, 2014

MVI Address 0xxx

1xxxx

3xxxx

4xxxx

Tag Address

1100

1601 to 1616

40091

ReadData[100]

1200

3201 to 3216

40191

ReadData[200]

1500

8001 to 8016

40491

ReadData[500]

1598

9569 to 9584

40589

ReadData[598]

1599

9585 to 9600

40590

ReadData[599]

With the offset parameters listed above, the Modbus Master could read from coils
10001 to 10176 using the tags MCM.DATA.W

RITE

D

ATA

[0]

TO

[9].

The Master

could also read from address 30001 to 30490, and the data contained in those
Modbus addresses would come from the tags MCM.DATA.W

RITE

D

ATA

[10]

TO

[499]

within the ControlLogix program.

The Master could then write to coils addressing 0001 to 0160 and this data would
reside within the ControlLogix program in tags MCM.DATA.R

EAD

D

ATA

[0]

TO

[9].

The Master could then write to registers using Modbus addresses 40001 to
40590, and this information would reside in addresses
MCM.DATA.R

EAD

D

ATA

[10]

TO

[599].

Note: The offset parameter only sets the starting location for the data. As shown above, if the
Master issues a Write command to address 40001, the data will go into the ControlLogix processor

at address MCM.DATA.R

EAD

D

ATA

[10].

Likewise, a Write To bit address 0161 will also change to address
MCM.DATA.R

EAD

D

ATA

[10].0

within the program. Be careful not to overlap your

data. You may want leave additional registers/bits unused to allow for future
expansion in the program.

3.3

Slave Configuration

Any parameters not mentioned in this section are not used when the module is
configured as a Modbus Master.

Value

Description

Enabled

1= enable port, 0 = disable port

Type

1= Modbus Slave Port

The module also supports a variety of Pass-Through modes. See
Pass-Through Blocks (page 129) for more information.

FloatFlag

As a Slave, emulates Enron/Daniel style floats. See Floating-Point
Data Handling (Modbus Slave) (page 63) for more information.

FloatStart

Register offset in message for floating data point. See Floating-
Point Data Handling (Modbus Slave) (page 63) for more
information.

Protocol

0 = Modbus RTU mode, 1 = Modbus ASCII mode

Baudrate

Sets the baud rate for the port. Valid values for this field are 110,
150, 300, 600, 1200, 2400, 4800, 9600, 19200, 384 or 3840 (for
38,400 baud), 576 or 5760 (for 57,600 baud) and 115,1152, or
11520 (for 115,200 baud)

Parity

0 = None, 1 = Odd, 2 = Even

DataBits

8 = Modbus RTU mode, 8 or 7 = Modbus ASCII mode