ProSoft Technology MVI71-GEC User Manual

Page 35

Advertising
background image

MVI71-GEC ♦ PLC 5 Platform

Diagnostics and Troubleshooting

Generic ASCII Ethernet Communication Module

User Manual

ProSoft Technology, Inc.

Page 35 of 86

May 11, 2011

4.1.2 Clearing a Fault Condition

Typically, if the OK LED on the front of the module turns RED for more than ten

seconds, a hardware problem has been detected in the module or the program

has exited.
To clear the condition, follow these steps:
1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed

correctly.

5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the

PLC controller.

If the module's OK LED does not turn GREEN, verify that the module is inserted

completely into the rack. If this does not cure the problem, contact ProSoft

Technology Technical Support.

4.1.3 Troubleshooting

Use the following troubleshooting steps if you encounter problems when the

module is powered up. If these steps do not resolve your problem, please contact

ProSoft Technology Technical Support.

Processor Errors

Problem description

Steps to take

Processor fault

Verify that the module is plugged into the slot that has been configured
for the module in the I/O Configuration of RSLogix.
Verify that the slot location in the rack has been configured correctly in
the ladder logic.

Processor I/O LED
flashes

This indicates a problem with backplane communications. A problem
could exist between the processor and any installed I/O module, not just

the MVI71-GEC. Verify that all modules in the rack are correctly

configured in the ladder logic.

Module Errors

Problem description

Steps to take

BP ACT LED (not

present on MVI56E

modules) remains OFF
or blinks slowly
MVI56E modules with
scrolling LED display:
<Backplane Status>
condition reads ERR

This indicates that backplane transfer operations are failing. Connect to

the module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:


The processor is in RUN or REM RUN mode.



The backplane driver is loaded in the module.



The module is configured for read and write data block transfer.



The ladder logic handles all read and write block situations.



The module is properly configured in the processor I/O configuration

and ladder logic.

OK LED remains RED

The program has halted or a critical error has occurred. Connect to the

Configuration/Debug port to see if the module is running. If the program
has halted, turn off power to the rack, remove the card from the rack and

re-insert it, and then restore power to the rack.

Advertising