SLC Files

M1: File Data
DNP Memory

DNP Master Device

IED Memory

DNP Slave Device

Digital Input File

Digital Input Data

Analog Input File

Analog Input Data

Counter Data File

Counter Data

Digital Output File

Digital Output Data

Analog Output File

Analog Output Data

Floating-Point
Data

DNP Master Device

Float Input

Floating-Point Input Data

Float Output

Floating-Point Output
Data

It is recommended to associate each individual data type with a separate file in
the SLC. This permits easier management of the ladder logic and expansion of
the system.

DNP Digital Input Data
This data type stores the binary value of 1 or 0. The size of this data area is
determined from the configuration parameter Number of Binary Input Points. The
data area is partitioned into two separate areas. The first is the DNP binary input
data acquired from the SLC, and the second is the binary input data from IED
units on the DNP master port. The configuration parameter, Number of Binary
Input Points for SLC, determines the size of the SLC's data area. The remaining
portion is defined as the IED binary input data area.

SLC data are transferred to the module from the SLC using the COP command
in the ladder logic. Therefore, these data are read-only for the module and the
DNP master unit communicating with the module. When the module receives a
new block of this data from the SLC, it compares the new values to those
currently in the database. If there is a change in any of the data, the module
generates an event message for the points that change.

Data from IED units can also be placed in the DNP binary input data area.
Commands in the command list must specify the DNP database address (point
number) where the data will be placed.