Reference

MVI46-DFNT ♦ SLC Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 148 of 177

ProSoft Technology, Inc.

October 12, 2010

The M

ESSAGE

C

ONFIGURATION

dialog box must be completed to define the data

set to transfer to the processor from the module. An example of the dialog box

follows:

Complete the dialog box for the data area to be transferred. CIP Data Table

messages require a tag database element for both the source and destination.

The D

ESTINATION

T

AG

is a tag defined in the ControlLogix Tag database. The

S

OURCE

E

LEMENT

is the tag element in the DFNT module. The module simulates

a tag database as an array of elements defined by the maximum register size for

the module (user configuration parameter "Maximum Register" in the [Module]

section) with the tag name

INT

_

DATA

.

In the example above, the first element in

the database is the starting location for the read operation of ten elements.

Additionally, the C

OMMUNICATION

information must also be configured. An

example of the dialog box follows: