// Server Side Connections
//

Connections
Adapter

, Protocol

N1

, Modbus/TCP



//==========================================================
//
// Server Side Nodes
//

Nodes

Node_Name , Node_ID , Protocol
MBP_Srv_11 , 11

, Modbus/TCP







//==============================================================
//
// Server Side Map Descriptors
//

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Address , Length
SMD_DI_01

, DA_DI_01

, 0

, Passive

, MBP_Srv_11 , 10001

, 200

SMD_DO_01

, DA_DO_01

, 0

, Passive

, MBP_Srv_11 , 00001

, 200

Adapter definition applies to defining network
and FieldServer (e.g. Profibus) connections.

A Node name for
reference by the
Map Descriptors.

Since the FieldServer is a Server here, this is the ID of the FieldServer (virtual)
Node. The FieldServer can represent multiple Virtual Node_ID’s in most protocols.

The protocol for the network
connected to this port.

Settings for how the FieldServer communicates with Client Nodes.