Dual-Compressor Module

Operation

14

2006SSD-75 R4 (10/10)

3.0 o

peratioN

3.1 Initial Startup - Compressor Module

The following inspections should be made on initial startup—-typically, by the Packager—and after long

periods of storage.

• Verify acceptable pre-startup conditions using the checklist in

3.1.1 - Pre-Startup Checklist.

• Start the Compressor Module, then perform the checks in

3.1.2 - Post-Startup Checklist.

3.1.1 Pre-Startup Checklist

Perform these checks BEFORE starting the Compressor Module:

MAIN POWER

Check for the following conditions:

___ 1. Motor type is correct for the application,

either Variable Speed (275V) or Fixed Speed

motor (480V).

___ 2. Power phasing to the terminal strip and

Compressors is correct.

___ 3. Supply voltage to the Variable Frequency

Drive (VFD) or Fixed Speed Compressor

motors is correct.

___ 4. Each Compressor motor is equipped with

current overload protection.

___ 5. Compressor motor overloads are configured

to inhibit the VFD or either fixed speed

Compressor if either motor overload opens.

___ 6. Compressor motor overloads are configured

for manual reset.

___ 7. Compressor motor overloads are set for

proper current.

___ 8. All chassis, earth grounds are connected.

___ 9. A load reactor or other approved filter is

installed for systems with power lead lengths

in excess of 200 ft. (61m) between the VFD

and Compressor Module terminal box.

LOW VOLTAGE DEVICES

Verify these conditions for low voltage devices:

___ 1. DC polarity is correct.

___ 2. Temperature control device—if other than

standard thermistor control—is working

properly.

SAFETY AND CONTROL DEVICES

Make sure that all safety and control switches

and devices are configured to inhibit Compressor

operation if a fault condition is detected, including:

___ 1. Low inlet pressure switch

___ 2. High discharge pressure switch

___ 3. High temperature switch

___ 4. Variable Frequency Drive (VFD) fault

___ 5. Motor overload trip

___ 6. Other safety and control switches and

devices

MECHANICAL SYSTEMS

Inspect for these conditions:

___ 1.

(Required) Compressor inlet is protected

from water slugging.

___ 2.

(Recommended) Gas filtration and

treatment is appropriate for the

application.

___ 3. Packager configuration applies back

pressure to the Compressors.

___ 4. Inlet and discharge valves allow the

module to be isolated.

___ 5. All guards and protective covers are

installed.

___ 6. Protection from freezing is provided if

needed for the application and location.

___ 7. A suitable enclosure providing protection

from the elements is appropriate for the

application and location.

3.1.2 Post-Startup Checklist

Perform these checks AFTER starting the Compressor Module:

DURING INITIAL OPERATION, PERFORM THESE CHECKS:

___ 1. Compressor Module builds pressure on initial startup; no unusual mechanical noise.

___ 2. Oil level is correct at minimum and maximum speeds.

___ 3. No gas leaks are present.

___ 4. No oil leaks are present.

___ 5. Oil cooler fans turn on and run at the appropriate temperature.

___ 6. Oil cooler fan speed varies with temperature.

___ 7. Compressor motor speed varies appropriately for the Packager configuration.

___ 8. Compressor continues to operate in bypass when the Compressor Module discharge is blocked.

___ 9. Compressor Module is leak tight (maintains approximately 30 psig or more when the Compressors are initially

turned off).