Appendix a – fault codes – Exide Technologies DEC200 User Manual

Page 14

Advertising
background image

Sales

• Service • Recycling 1-888-563-6300

13

APPENDIX A – FAULT CODES

CODE

STATUS

DESCRIPTION

F01

N

Over discharged battery (<1.90vpc after 30 seconds of charge)

F02

N

Deep discharged battery (<1.90vpc after 30 seconds of charge > 1.90vpc)

F03

N

Sulphated battery

F04

S

Charger over heating

F05

S

Mains failed during charge

F06

R

No output current

F07

C

Incorrect battery < 1.70

F07 (+Y led on)

C

Incorrect battery > 2.25

F09

C

Bulk charge time-out

F10

C

Second stage time-out (Profile Dependant)

F11

C

Incorrect Mains Frequency

F12

C

Control hardware (MCU)

F13

S

Thermistor fault

F16

S

Battery overheating (if temp probe fitted)

F17

C

Auto balance charge time-out

F18

C

Battery disconnected without pausing charge

F22

C

di/dt termination

Key: -
C
= critical fault

Ö charge stopped Ö fault code displayed permanently

S = suspend fault

Ö charge suspended until criteria fulfilled Ö fault code displayed permanently

R = retry fault

Ö charge retries after 20 seconds Ö fault code display alternating with standard

display

N = non-critical fault

Ö charge continues Ö fault code display alternating with standard display







Advertising