Table 1 – input voltage choices – Exide Technologies DEC200 User Manual

Page 6

Advertising
background image

Sales

• Service • Recycling 1-888-563-6300

5

6. AC ELECTRICAL SUPPLY

The charger must be connected to either a single phase or three phase, 60 Hertz
(

± 2%) AC power source. Three phase chargers cannot be powered with a single

phase source.

The following transformer options are available:

TABLE 1 – INPUT VOLTAGE CHOICES

Single phase

Three phase

208/240/480VAC, 60Hz

208/240/480VAC, 60Hz


Only the AC input wire configuration for multi-input chargers can be changed. Follow
Figure 1 (page 6) for single-phase input or Figure 2 (page 7) for three-phase input
transformers. A qualified electrical contractor should perform this adjustment.

6.1. BRANCH CIRCUIT PROTECTION

The charger comes with an internal supplementary protective device rated to
accommodate the highest possible current and voltage for that model.

CAUTION: TO REDUCE THE RISK OF FIRE, USE ONLY ON CIRCUITS PROVIDED

WITH BRANCH CIRCUIT PROTECTION CONSISTENT WITH THE
CURRENT INDICATED ON THE FRONT PANEL-RATING LABEL AND
IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,
ANSI/NFPA 70.