Troubleshooting, Roubleshooting, Led status diagnosis/audible alarm – Emerson GXT2U User Manual

Page 29

Advertising
background image

25

T

ROUBLESHOOTING

The information below indicates various symptoms a user may encounter in

the event the Liebert GXT2U develops a problem. Use this information to

determine whether external factors caused the problem and how to remedy

the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illumi-

nated to provide a diagnostic aid to the operator, as described below:

Under fault conditions, the Fault indicators will be illuminated indefinitely

while battery charger is operational, or for a maximum of 5 minutes while

battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or

contact the Liebert Worldwide Support Group. Please have the UPS model

number and serial number available at the time of your inquiry.

LED

Status

Diagnosis/Audible alarm

All LEDs

On bypass due to output overload; beep every half-second

A LED

On bypass due to overtemperature condition; beep every 4 sec.

B LED

On bypass due to DC bus overvoltage; beep every 4 sec.

C LED

On bypass due to control power supply failure; beep every 4 sec.

D LED

On bypass due to PFC failure; beep every 4 sec.

E LED

On bypass due to inverter failure; beep every 4 sec.

A&C LEDs

UPS failed battery test; long beep every minute

C&E LEDs

UPS shutdown due to command from communication port (SNMP); no beep

Battery LED

Flashing

Internal Battery source not available (continuous horn). Check battery

connection, completely power down and reboot UPS.

AC LED

Flashing

Line-to-neutral reversal in the AC input power supply or a loss of proper

grounding; continuous horn and UPS will not start.

Bypass LED

Flashing

Utility power voltage or frequency is out of tolerance; bypass is unavailable.

This example shows the UPS

on bypass due to output overload.

Fault

E

D

C

B

A

A

B

C

D

E

Fault

AC INPUT BATTERY UPS ON BYPASS

BATTERY

UPS ON

BYPASS

AC

INPUT

LOAD/BATTERY

LEVEL INDICATORS

Advertising