Preinstallation, Locating the air filter – Emerson MEDIA AIR CLEANER ACM2000M-XXX User Manual

Page 4

Advertising
background image

4

PREINSTALLATION

LOCATING THE AIR FILTER

Your air fi lter must be mounted in the return air duct of a central
forced-air system, on the air entering side of your furnace. (See
Figure 3 for example).

Select a location that meets the following:

1. The face of the fi lter will be at a right angle to the air

stream.

2. Allow 25” of clearance in front of the air fi lter compartment

door to permit removal of fi lters.

See fi gure 4 for complete compartment dimensions.

AIR FLOW

FURNACE
OPENING

TRANSITION SECTION
(IF NEEDED)

AIR CLEANER

OPENING

LOCATING THE AIR FILTER

AN AIR FILTER MUST BE MOUNTED IN THE RETURN AIR DUCT OF A CENTRAL
FORCED-AIR SYSTEM, ON THE AIR ENTERING SIDE OF FURNACE.

NOT TO EXCEED 20°

DUCTWORK

AIR FLOW

AIR CLEANER

FURNACE

Figure 3

Model NO.

A

B

C

CFM RATING

LENGTH

HEIGHT

WIDTH

ACM1000M-XXX

19-13/16

18-5/16

5-7/16

600 TO 1200

ACM1400M-XXX

24-13/16

18-5/16

5-7/16

1000 TO 1600

ACM1600M-XXX

19-13/16

22-5/16

5-7/16

1200 TO 1800

ACM2000M-XXX

24-13/16

22-5/16

5-7/16

1800 TO 2200

C

B

A

Figure 4

3. The air fi lter is not to be placed in the discharge of either the

heating or cooling unit.

4. IMPORTANT: If atomizing spray type humidifi er is used, it

must be installed downstream from the air fi lter.

If furnace opening cannot be enlarged to required size, a
transition sheet metal section must be used. Transition must
be planned for each job. Reduction should not be more than
4 inches per linear foot, approximately 20 angular degrees
(Figure 3).