Specifications

Diagnostic LEDs

Wiring Specifications

Ordering Information

Power

24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W

Dimensions

W x D x H: in. (mm)

Module:

11.295 x 0.56 x 7.5 (286.9 x 14.2 x 190.5)

Enclosure (painted steel):

14.25 x 2.85 x 12 (362 x 72.4 x 304.8)

Communication

• One (1) Ethernet 10/100BaseT RJ-45 port

• One (1) Configurable Serial Port - EIA-232 or 485 (2- or 4-wire)

• 5-position Terminal Block

• One (1) CMnet EIA-485 Port - Control Module network screw terminals

• Switch-selectable baud rates ARC156 / 9600 or 38.4bps

• Recommended wire: MAGNUM Cable P/N A3-ARC-156-2

BACnet Port (ARCNET156 or EIA-485 communication): In ARCNET156 mode, the port speaks

BACnet ARC156. In EIA-485 mode, DIP switch settings specify baud rate and protocol: BACnet

MS/TP or Modbus (RTU or ASCII).

Port S1 (BMS connection): Normally configured for a Building Management System; may be

configured for EIA-485 or EIA-232. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or

ASCII) protocols.

Port S2 (MFR connection): Connection to manufacturer’s equipment; jumper enables EIA-485 or

EIA-232 mode. Supports BACnet MS/TP, BACnet PTP and Modbus (RTU or ASCII) protocols.

Rnet: Local laptop and/or BACview access port. Conforms to the BACnet Advanced Application

Controller (B-AAC) Standard Device as defined in BACnet 135-2001 Annex L.

Environmental

Operating Range

20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing.

Note: Control modules should be installed within the building.

Memory

16 MByte non-volatile battery-backed SDRAM (with 12 MBytes available for use)

8 MByte Flash memory, 32-bit memory bus

Protection

Built-in surge and transient protection circuitry

Battery

3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation

Fault Detection

Hardware watchdog timer

Agency Listings

UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 - Subpart B - Class A

Indicator

Description

Indicator

Description

BACnet transmit Blinks when data is transmitted

Port S1 transmit Blinks when data is transmitted

BACnet receive

Blinks when data is received

Port S1 receive

Blinks when data is received

Archive Valid

N/A

Battery low

Blinks when the battery is low

Connection

Supported Wire Types

Maximum Wire Length

Rating

Ethernet 10 BaseT

CAT 5

328 ft. (100m)

N/A

Port S1 ARCnet

MAGNUM Cable P/N A3-ARC-156-2

3000 ft. (915m)

N/A

Port S2 EIA-485

18-22 AWG Stranded & Shielded; 18 AWG* (recommended)

Non Plenum - Belden 9461; Plenum - Belden 88761

1000 ft. (300m)

N/A

Port S2 EIA-232

18-22 AWG Stranded & Shielded; 18 AWG* (recommended)

Non Plenum - Belden 9461; Plenum - Belden 88761

50 ft. (15m)

N/A

Quantity

Part #

Description

SiteTPI-E

SiteScan Web Third-Party Interface Module - Ethernet Ready