Site Planning Data, Liebert Npower: 30-130kVA, 60 Hz, 208 or 480VAC

UPS

Rating

Voltage

Standard AC Input

AC Input w/Filter Opt.

Battery

AC Output

Mechanical Data

Current (A)

Rec.

OCPD

Current (A)

Rec.

OCPD

Nom.

VDC

Battery

kW

Max.

Discharge

Current

Dimensions

WxDxH, in. (mm)

Weight

lb. (kg)

Floor Loading

lb./ft

2

(kg/m

2

)

Heat Dis.

BTU/h (kWH)

Cooling Air
CFM (m

3

/h)

kVA

kW

Input

Output Nom.

Max.

Nom.

Max.

Nom

OCPD

30

24

208

208

92

114

150

80

99

125

480

26

66A

83

125

31.7x32.5x71

(805x825x1800)

2100 (953)

294 (1435)

8,500 (

2.5

)

720

(1223)

30

24

480

208

38

48

60

33

41

50

480

26

66A

83

125

1850 (839)

259 (1265)

7,500 (2.2)

30

24

480

480

38

48

60

33

41

50

480

26

66A

36

50

259 (1265)

7,500 (2.2)

40

32

208

208

122

153

200

106

133

175

480

34

88A

111

150

31.7x32.5x71

(805x825x1800)

2200 (998)

307 (1499)

11,000 (

(3.2)

720

(1223)

40

32

480

208

51

64

80

44

55

70

480

34

88A

111

150

1900 (862)

266 (1299)

10,000 (2.9)

40

32

480

480

51

64

80

44

55

70

480

34

88A

48

60

266 (1299)

10,000 (2.9)

50

40

208

208

153

191

250

133

166

200

480

43

109A

139

175

31.7x32.5x71

(805x825x1800)

2200 (998)

307 (1499)

14,000

(4.1)

720

(1223)

50

40

480

208

64

80

100

55

69

100

480

43

109A

139

175

1900 (862)

266 (1299)

12,000 (3.5)

50

40

480

480

64

80

100

55

69

100

480

43

109A

60

80

266 (1299)

12,000 (3.5)

65

52

208

208

193

242

300

171

213

300

480

55

141A

180

225

39.4x32.5x71

(1001x825x1800)

2500 (1134) 281 (1372)

18,000

(5.3)

960

(1631)

65

52

480

208

80

99

125

70

88

125

480

55

141A

180

225

2150 (975)

242 (1182)

15,000 (4.4)

65

52

480

480

80

99

125

70

88

125

480

55

141A

78

10

242 (1182)

15,000 (4.4)

80

64

208

208

238

298

400

210

262

350

480

68

174A

222

300

39.4x32.5x71

(1001x825x1800)

2500 (1134) 281 (1372)

22,000

(6.4)

960

(1631)

80

64

480

208

98

122

150

87

108

150

480

68

174A

222

300

2150 (975)

242 (1182)

18,000

(5.3)

80

64

480

480

98

122

150

87

108

150

480

68

174A

96

125

242 (1182)

18,000

(5.3)

100

80

208

208

296

370

450

261

326

400

480

85

218A

278

350

49.2x32.5x71

(1250x825x1800)

3350 (1520) 302 (1474)

26,000

(7.6)

)

1440

(2447

100

80

480

208

122

152

200

108

135

175

480

85

218A

278

350

2800 (1270)

252 (1230)

21,000 (6.1)

100

80

480

480

122

152

200

108

135

175

480

85

218A

120

150

252 (1230)

21,000 (6.1)

130

104

208

208

385

481

600

336

420

500

480

111

283A

361

450

49.2x32.5x71

(1250x825x1800)

3350 (1520) 302 (1474)

33,000

(9.7)

1440

(2447)

130

104

480

208

158

198

250

140

175

225

480

111

283A

361

450

2800 (1270)

252 (1230)

27,000 (7.9)

130

104

480

480

158

198

250

140

175

225

480

111

283A

156

200

252 (1230)

27,000 (7.9)

See Notes for Table (below):

1

2,3,8,12 6,14

1

2,3,8,12

6

4

1,3,5,8,12 1,3,8,12

6

13

13, 14

Notes for Table

1.

Nominal (Nom) current is based on full rated output load.

2.

Maximum (Max) current (125% of nominal) is short duration for battery recharge

conditions.

3.

UPS input and bypass cables must be run in separate conduit from output cables.

4.

Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.

5.

Power cables from UPS DC link to batteries should be sized for a total maximum 2.0V line

drop (measured at the UPS) at maximum discharge current.

6.

OCPD=Overcurrent Protection Device. Recommended AC input and AC output overcurrent

protection represents 125% of nominal full load current (continuous) per NEC 215.

7.

Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground

conductors are recommended. Neutral conductors to be sized for full capacity per

NEC 310-15(b)(4). References are per NEC 1999.

8.

Wiring requirements:

AC Input and Output: 3-phase, 3- or-4-wire plus ground, depending on UPS configuration.

See Installation Manual and submittal drawings for specific instructions.

DC Input: 2-wire (positive and negative), plus ground.

9.

All wiring is to be in accordance with national and local electrical codes.

10. Minimum access clearance is 3 ft. (0.9m) front and 1 ft. (0.3m) above UPS.
11. Top or bottom cable entry through removable access plates. Punch plate to suit conduit

size, then replace.

12. Control wiring and power wiring must be run in separate conduit.
13. Weights and dimensions shown do not include battery cabinet, Slim-Line distribution

cabinet or other options.

14. Add 560 lb. (254kg) for 100-130kVA unit with dual input and isolated 208VAC output.
15. Backup emergency generator must be properly sized and equipped with an isochronous

governor (generator frequency regulation) and a UPS-compatible voltage regulator.

16. An on-site automatic transfer switch should be equipped with auxiliary contacts for UPS

“on generator” current limit. Refer to Liebert publication 91K-PLT-48-02.

17. An external isolated maintenance bypass circuit might cause utility AC input to be out of

phase with the UPS AC output.

© 2004 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names

referred to are trademarks or registered trademarks of their respective owners.

SL-24531 (11/04) Rev. 4

Liebert Corporation

1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229

Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com

Advertising