Enerco | enerRadiant® XL Series Heater

Operating Instructions and Owner’s Manual

SECTION 6

Wiring

Heaters are normally controlled by thermostats. Line voltage
thermostats are wired directly (see Figure 18a), the recommended
24V thermostats use a relay (see Figure 18b). Heaters must be
grounded in accordance with the National Electric Code ANSI/NFPA -
70 - latest version. Heaters may also be controlled with a manual line
voltage switch or timer switch in place of the thermostat.

FIGURE 18a: Line Voltage Thermostat Wiring

T

H

N

120v – 60 Hz

White

White

Green

Green

Supply Circuit

120v – 60 Hz

Supply Circuit

Burners

(Maximum – 2 per Thermostat)

Burners

(Maximum – 1 per Thermostat)

Black

Black

H

N

T

FIGURE 18b: Low Line Voltage Thermostat Wiring

T

H

N

120v – 60 Hz

White

White

Green

Green

Supply Circuit

120v – 60 Hz

Supply Circuit

Burners

(Maximum – 2 per Thermostat)

Burners

(Maximum – 1 per Thermostat)

Black

Black

H

N

T

FIGURE 20: Ener-Radiant XL Burner Internal Wiring

B

C

W

Black

Black

White

White

Burner 3

120V – 60Hz

Supply Circuit

Burner 1

Burner 2

Burner 4

White

N

H

N

H

Red

Red/Yellow*

Purple*

Black

Green

Whit

e

G

Y

3

6

5

4

2

T

Transformer Relay

FIGURE 19: Wiring of Low Voltage Thermostat and Relay

When using 1-2 burners, use SPDT Transformer Relay / Stk. # 00172

When using 3-4 burners, use DPDT Transformer Relay / Stk. # 00183

Wires marked with an asterisk (*) are for use only with DPDT
Transformer Relay.

If any of the original wire as supplied with the
appliance must be replaced, it must be replace with
wiring material having a temperature rating of at least
105°C and 600 volts.

Each burner must be electrically grounded in
accordance with the National Electric Code ANSI/NFPA
- 70 - latest version.

FIGURE 21: Ener-Radiant XL Burner Internal Wiring Ladder
Diagram

VAC

120

120V

24V

Black

Black

Purple

Yello

w

Yello

w

Black

Black

Black

Green

Green

Orange

Transformer

White

White

White

THERMOSTAT

White

Blue

Gas Valve

Air Switch

Ignitor

Sensor

Motor / Blower

Door Switch

Terminal

Bushing

120V

L2

(NEUTRAL)

White

White

White

White

White

White

Gray

Orange

Transfomer

Thermostat

Air Switch

Gas Valve

Door Switch

Motor / Blower

Ignitor

Sensor

Blue

Yellow

Yellow

Purple

Black

Black

Black

Black

L2 (HOT)

24V

Low Voltage Thermostat

Stk. #10368