Table 17, Interconnect wiring—1+n type c connection to nx – Emerson Liebert NX 10-30kVA User Manual

Page 63

Advertising
background image

Installation Drawings

55

Figure 42 Lineup detail—1+N Type C connection to NX

Table 17

Interconnect wiring—1+N Type C connection to NX

Run

From

To

Conductors

A

Utility AC Source

Paralleling Cabinet

Ph A, B, C-system Input

B

Utility AC Source

Paralleling Cabinet

Ground - System Input

C1-C4

Paralleling Cabinet

UPS #1-UPS #4 Module AC Input

Ph A ,B, C - UPS Input

D1-d4

Paralleling Cabinet

UPS #1-UPS #4 Module AC Input

Neutral - UPS Input

E1-E4

UPS #1-UPS #4 Module AC Output

Paralleling Cabinet

Ph A, B, C - UPS Output

G1-G4 UPS #1-UPS #4 Module AC Output

Paralleling Cabinet

Neutral - UPS Output

H1-H4

Paralleling Cabinet

UPS #1-UPS #4 Module AC Ground

Ground - UPS

I

Paralleling Cabinet

Load AC Connection

Ph A ,B, C - Load

J

Paralleling Cabinet

Load AC Connection

Ground - Load

K

Paralleling Cabinet

Load AC Connection

Neutral - Load

L1-l4

Paralleling Cabinet

UPS #1-UPS #4 Module

UPS Parallel Logic Board (M3)

Output Breaker Aux Contact

M1-M4

Paralleling Cabinet

UPS #1-UPS #4 Module

UPS Parallel Logic Board (M3)

Rotary Switch Aux Contact

1 + N Parallel Cabinet

(front view without front door and panel)

1 + N Cabinet Side View

(without side panel or door)

1 + N Cabinet Interior View

(neutral and ground busbar location)

UPS Module Left Side View

(without side panel)

1. All Liebert-supplied cable must be repositioned prior to and while

setting the cabinets in their installed location.

2. All interconnection cables and hardware supplied by others.
3. AC connections must be made to the UPS modules before attaching

paralleling cabinet to UPS modules.

4. Utility AC source neutral not required for maintenance bypass/

transformer cabinet Type C.

5. The interconnecting input cables between the paralleling cabinet and

the UPSes must be the same size and the same length.

6. The interconnecting output cables between the paralleling cabinet

and the UPSes must be the same size and the same length.

7. The location of the system output neutral busbar (connection K) and

the ground busbar (connections H, I and J) are shown for a left-access

style. For right-access version, these busbars are at opposite locations.

8. Refer to the individual drawing of each piece of equipment for

additional details.