Mantle clearances, Initial installation – Enviro C-10791 User Manual

Page 14

Advertising
background image

3"

(76mm)

12"

(305mm)

6"

(152mm)

14"

(356mm)

Top of unit

3” (76mm) mantle

10" (254mm) mantle

Combustible front face

3

/

4

" (19mm) facing board

Figure 18. Combustible Mantle Clearances.

Initial Installation

QUALIFIED INSTALLERS ONLY

14

A shelf may be installed above the unit. We

recommend that no heat sensitive items or

components be placed on the shelf (see

Figure 17).

M

ANTLE

C

LEARANCES

:

It is not necessary to install a mantle, but if one is desired it is important to follow the guidelines.
Top of unit to horizontal framing:

3”

(7.6 cm)

Top of unit to bottom of 31⁄2” (8.9 cm) mantle: 8”

(20.3 cm)

Top of unit to bottom of 10” (25.4 cm) mantle: 10” (25.4 cm)

3"

(76mm)

Top of unit

Combustible

front face

Combustible board

Figure 17. Combustible Shelf Clearance.

Figure 16. Raised Fireplace with no Hearth

Even though the DV36 can be installed at floor

level without a hearth, there are a few options

with raised fireplaces: raised with a floor level

hearth (Figures 14), raised with a raised hearth

(Figures 15), or raised with no hearth (Figures

16). If the fireplace is raised, it cannot be placed

within 37 inches (1.04 m) of the ceiling. When

installing a raised fireplace, it is imperative that

the support stand is strong enough to hold the

weight of the fireplace and venting.