Connection to the gas supply
should be with either rigid or semi-
rigid pipe, i.e. steel or copper.

The connection should be suitable
for connection to RC ½ (½ BSP
male conical thread).

When the final connection has been
made, it is essential that a thorough
leak test is carried out on the hob
and installaion.

Ensure that the main connection
pipe does not exert any strain on
the hob.

It is important to install the
elbow correctly, with the
shoulder on the end of the
thread, fitted to the hob
connection pipe.

Failure to ensure to correct
assembly will cause leakage
of gas.

Pressure test

The unit should be pressure-tested
at Max. 150 mbar.