Step 3, Run the required wires, See illustration 2) – Echo 8870 User Manual

Page 5: Illustration 2 – run wire for system

Advertising
background image

CATEGORY 5 (4-PAIR TWISTED)
COMMUNICATION WIRE

INSTALLATION TIP: USE A
PIECE OF TAPE TO
IDENTIFY WHICH
THERMOSTAT EACH CABLE
IS RUN TO

ZONE DAMPERS

2-WIRE
THERMOSTAT
CABLE

MODEL 8027 PLUG-IN

TRANSFORMER

(FOR COMMUNICATION SYSTEM)

2-WIRE THERMOSTAT CABLE

SEE ZONE CONTROL SYSTEM

INSTALLATION LITERATURE

FOR COMPLETE ZONE

SYSTEM WIRING

REQUIREMENTS

SINGLE ZONE

HVAC EQUIPMENT

DISTRIBUTION PANEL

USE 2-WIRE THERMOSTAT

CABLE TO CONNECT OFF-

BOARD SENSORS SUCH AS

THE MODEL 8051 FLUSH

MOUNT SENSOR TO

SUPPORT MODULES.

SUPPORT MODULE

THERMOSTAT 3

THERMOSTAT 4

THERMOSTAT 2

THERMOSTAT 1

ZONE CONTROL SYSTEM

RX

TX

DATA

RS-232

RX

TX

ENABLE

RS-485

RX

TX

DATA

RS-485

POWER

Model 8811 Protocol Adapter

Power

7.5VAC

RS-485

RS-485

RS-232

4000 FT.

MAX.

4000 FT

. MAX.

4000 FT

. MAX.

4000 FT

. MAX.

4000 FT.

MAX.

1000 FT.

MAX.

NOTE: TOTAL DISTANCE FROM
PROTOCOL ADAPTER TO THERMOSTAT
NOT TO EXCEED 4,000 FEET

THERMOSTAT CABLE
5 thru 8 CONDUCTOR

ILLUSTRATION 2 – Run Wire For System

3

RUN THE REQUIRED WIRES

(SEE ILLUSTRATION 2)

Step 3

1. Run thermostat cable from each thermostat to the

appropriate HVAC system or zone control panel. Use 4
through 8-conductor thermostat cable depending on the
type of equipment and number of equipment stages. Run
one more wire than would be required if connecting to a
mechanical thermostat.
❖ If you are using remote temperature or humidity

support modules as part of your installation, now is the
time to run the additional wires for these items. A
separate Category 5 cable must be run from thermostat
to support module.

2. At the HVAC/zone control system, use a piece of tape to

label the location of the thermostat on the cable as you go.

3. Run Category-5, 4-pair twisted cable (8-conductor) from

each thermostat to the Distribution Panel.

4. At the Distribution Panel, use a piece of tape to

label

the location of the thermostat on the cable as you go.

5. Run Category-5 wire from the Distribution Panel to the

Protocol Adapter. If more than one Distribution Panel is
used, run Category-5 wire between each panel.

6. Run two-conductor thermostat cable from the

Model 8027 Transformer to the Distribution Panel. You
can use Category-5 wire, but you must use one pair of
wires per terminal.