Sequence of Operation --- Utility Failure

Series 185

7

381333–319 D

wait 10 sec.

for generator

to warm up

generator runs

unloaded

for 2 min.

generator

starting

Utility fails

(longer than

3 sec.)

generator

stops

wait 5 min.

for utility

to stabilize

observe

these

power

lights

observe

these

switch

lights

waiting for utility

to return

light is on

light is off

utility acceptable

generator off

Utility power good.

Electrical loads on utility

¡

£

electrical loads

switched to generator

start

generator

©

electrical loads

switched back

to utility

¥

¢

generator

acceptable

¤

utility

returns

load on utility

utility off

generator acceptable

load on generator

utility off

generator off

load off

utility off

generator

acceptable

load on utility

utility acceptable

generator

acceptable

load on utility

utility

acceptable

generator acceptable

load on generator