SL-31080 Product Specification/Installation Sheet

page 2

6/03 (Rev. 0)

Mounting

Enclosure Mounting Instructions

Mounting hardware is provided for both junction box
and drywall installation.

1. Pull the wires through the opening in the base

plate.

2. For junction box installation: Secure the

base to the box using the #6-32 x 1/2" mounting
screws provided.
For drywall installation: Drill two 3/16" holes
3-1/4" apart on center. Insert the drywall
anchors and secure the base using the #6 x 1"
sheet metal screws provided.

3. Terminate the unit according to the guidelines

in Termination on page 1.

4. Attach the cover by latching it to the top of the

base, rotating the cover down and snapping it
into place.

5. Secure the cover by backing out the lock-down

screws using a 1/16" allen wrench until they are
flush with the bottom of the cover.

Troubleshooting Guide

The following table lists common problems and possible solutions. For more information, consult your local

dealer, Liebert representative or the Liebert Worldwide Support Group.

Junction box

2" x 4"

Mounting

screws

Cover

Delta

base

Wall

Locking

screws

NOTE
In a wall-mount application, the wall temperature and the

temperature of the air within the wall cavity can cause

erroneous readings. The mixing of room air and air from

within the wall cavity can lead to condensation and premature

failure of the sensor.
To prevent these conditions, seal the conduit leading to the

junction box and seal the hole in the drywall by using an

adhesive backed, foam insulating pad.

Problems

Possible Solutions

Unit will not operate

• Check +24 VDC power supply at controller.
• Disconnect the sensor and check power wires for +24 VDC.

Humidity reading is maximum

20 mA or 100%

• Make sure the sensor is installed properly, and is not shorted.
Quick Check: Remove the sensor. If the reading does not change, contact technical

support.

Humidity reading is minimum

4 mA or 0%

• Verify that the humidity sensor installed.
Quick Check: Short the sensor terminal block with a wire. Does the reading change? If so,

the sensor may be faulty; if not, contact technical support.

Humidity reading in software

appears to be off more than

specified accuracy

• Check all software parameters.
• If available, check the sensor against a calibrated control such as a hygrometer.
• Determine if the sensor is exposed to an external source more than room.

Temperature sensor in front-

end software is reading high

• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.

Temperature sensor in front-

end software is reading low

• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.