900 specifications – Eaton Electrical 0800-2000 User Manual

Page 23

Advertising
background image

22

900 Specifications

* Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the

U.S. and Canada.

** At 0.7 leading or distortion power factor. Size output protection according to all applicable local or national codes.

*** Height includes switch.

Model

0800-2000
2 kVA/1.4 kW

0800-3000
3 kVA/2.1 kW

0800-4500
4.5 kVA/3.2 kW

0800-6000
6 kVA/4.2 kW

0800-7500
7.5 kVA/5.3 kW

AC Input Voltage
and Current

110 = 22 amps
115 = 22 amps
120 = 22 amps
127 = 22 amps
208 = 12 amps
220 = 12 amps
230 = 12 amps
240 = 12 amps

110 = 30 amps
115 = 30 amps
120 = 30 amps
127 = 30 amps
208 = 16 amps
220 = 16 amps
230 = 16 amps
240 = 16 amps

110 = 40 amps
115 = 40 amps
120 = 40 amps
127 = 40 amps
208 = 20 amps
220 = 20 amps
230 = 20 amps
240 = 20 amps

208 = 28 amps
220 = 28 amps
230 = 28 amps
240 = 28 amps

208 = 36 amps
220 = 36 amps
230 = 36 amps
240 = 36 amps

Recommended Input
Service for 60 Hz U.S.
Models*

120 = 30-amp
208 = 15-amp
240 = 15-amp

120 = 40-amp
208 = 20-amp
240 = 20-amp

120 = 50-amp
208 = 25-amp
240 = 25-amp

208 = 35-amp
240 = 35-amp

208 = 45-amp
240 = 45-amp

Output Voltage and
Maximum Output
Current in Amps**

120 = 16 amps
127 = 15 amps
208 = 9 amps
220 = 9 amps
230 = 8 amps
240 = 8 amps

120 = 25 amps
127 = 23 amps
208 = 14 amps
220 = 13 amps
230 = 13 amps
240 = 12 amps

120 = 37 amps
127 = 35 amps
208 = 21 amps
220 = 20 amps
230 =19 amps
240 = 18 amps

120 = 50 amps
127 = 47 amps
208 = 28 amps
220 = 27 amps
230 = 26 amps
240 = 25 amps

120 = 62 amps
127 = 59 amps
208 = 36 amps
220 = 34 amps
230 = 32 amps
240 = 31 amps

Efficiency on AC Line

90%

90%

90%

89%

89%

On Line BTU/hour:

kW/hour:

703
0.206

1024
0.300

1427
0.418

1707
0.500

2116
0.620

Audible Noise (dB)

<45 dB

<45 dB

<45 dB

<45 dB

<45 dB

Typical Standard

Runtime (minutes)

Full Load:

Half Load:

11 minutes
23 minutes

17 minutes
36 minutes

10 minutes
22 minutes

16 minutes
38 minutes

12 minutes
27 minutes

Weights:

No Internal Bypass,
Standard Batteries:

Internal Bypass,
Standard Batteries:

Battery Cabinet,
Standard Batteries:

FBT21
FBT22
FBT31
FBT32

280 lbs. (127 kg)

303 lbs. (137.4 kg)

235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)

327 lbs. (148.3 kg)

350 lbs. (158.8 kg)

235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)

383 lbs. (173.7 kg)

410 lbs. (186 kg)

235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)

563 lbs. (255.4 kg)

590 lbs. (267.6 kg)

235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)

635 lbs. (288 kg)

662 lbs. (300.3 kg)

235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)

Battery Cabinet
Dimensions (H x W x D)

UPS Dimensions with
Internal Bypass
(H*** x W x D)

UPS Dimensions
(without bypass)
(H x W x D)

28.6 x 13.5 x 35 inches

730 x 345 x 890 mm

27.25 x 13.5 x 28.5 inches

695 x 345 x 725 mm

31.9 x 13.5 x 31.5 in
810 x 347 x 800 mm

30.5 x 13.5 x 25 in
775 x 347 x 635 mm

FBT21, FBT22: 27.25 x 13.5 x 28.5 in. (695 x 345 x 725 mm); add 2.6 in/66 mm to depth for connection box.
FBT31, FBT32: 38.75 x 13.5 x 32.5 in. (985 x 345 x 825 mm); add 2.6 in./66 mm to depth for connection box.

40.1 x 13.5 x 39 inches

1020 x 345 x 990 mm

38.75 x 13.5 x 32.5 inches

985 x 345 x 825 mm