Emerson EC20 Series PLC RS-232 (DOP-A/AE/AS User Manual

Page 3

Advertising
background image

Series HMI Connection Manual


Definition of PLC Read/Write Address

a. Registers

42

V1.01 Revision November, 2011

Format

Type

Word No. (n)

Read/Write Range

Data

Length

Note

Data Word D

Dn

D0 – D7999 Word

Special Data Word SD

SDn

SD0 – SD255 Word

3

Data Word Z

Zn

Z0 – Z15 Word

Timer T

Tn

T0 – T255 Word

Counter C

Cn

C0 – C199 Word

Double word Counter CDW

CDWn

CDW200 – CDW255 Double

Word

Double word Data Word DDW DDWn

DDW0 – DDW7998 Double

Word

b. Contacts

Format

Type

Bit No. (b)

Read/Write Range

Note

External Output Relay Y

Yb

Y0 – Y377

Octal

External Input Relay X

Xb

X0 – X377

Octal

Internal Relay M

Mb

M0 – M1999

Special Internal Relay SM

SMb

SM0 – SM255

3

Status Relay S

Sb

S0 – S991

Timer T

Tb

T0 – T255

Counter C

Cb

C0 – C255

NOTE

1) Emerson EC20 series PLC has two communication ports, COM0 and COM1. They are

provided for the communication protocol for connecting to PC, Modbus communication
protocol and user-defined protocol. The default setting is COM0 to be enabled only, so the
user needs to set the communication mode as Modbus RTU via PC software before using it.

2) COM1 supports RS-232 and RS-485.

3) Please note that not all of the addresses can be written when reading SM and SD device. We

recommend the user not to set all of the addresses as write address except when setting
parameters.