Table 1. Specifications

Product Types

Type HF340: Standard 35 mm DIN rail mounting

with filtering components.
Type HF341: Standard 35 mm DIN rail mounting

without filtering components (straight through with

capacitor blocking on COMM terminals).

Connections

Three 2-pin Cage-clamp style connectors

accept up to 12 AWG wire

Power Requirements (Type HF340 only)

Input Current: 4−20 mA DC (nominal)

Input Voltage: At 20 milliamps DC, 2 volts above

input voltage required by the field instrument (2

volt drop across filter at 20 milliamps DC)

Filter Output

Filter output is clamped at 15 volts DC. Filter load

voltage requirement must not exceed 14 volts DC

Ambient Operating Temperature

−40 to 85_C (−40 to 185_F)

Ambient Relative Humidity

5 to 95%

Electromagnetic Interference (EMI)

These units have the CE mark in accordance with

the European Electromagnetic Compatibility

(EMC) Directive. They meet the emissions

requirements of IEC 61326-1 (Edition 1.1) for

Class A equipment for use in industrial locations

and Class B equipment for use in domestic

locations. They also meet the immunity

requirements listed in table 2 below. This table is

in accordance with Annex A of IEC 61326-1 for

equipment intended for use in industrial locations.

Dimensions

75 mm (3 inches) long by 12.5 mm (0.5 inches)

wide by 60 mm (2.4 inches) deep

Approximate Weight

0.1 kg (4 oz)

Table 2. EMC Immunity Performance Criteria

Port

Phenomenon

Basic Standard

Performance Criteria

Enclosure

Electrostatic discharge (ESD)

IEC 61000-4-2

A

EM field

IEC 61000-4-3

A

Rated power frequency magnetic field

IEC 61000-4-8

N/A

(1)

I/O signal/control

Burst

IEC 61000-4-4

A

Surge

IEC 61000-4-5

A

Conducted RF

IEC 61000-4-6

A

1. Not applicable; only applicable to magnetically sensitive equipment.

The filter is normally installed near the field wiring

terminals of the control system I/O. HART

communication is only possible between the filter

and the field instrument and at the filter COMM

terminals, but not on the control system side of the

filter. The filter is not designed or intended for use in

the process environment. Neither the filter nor its

outputs are approved for hazardous areas. However,

a recommended intrinsic safety barrier can be

connected between the FIELDVUE instrument and

the filter in intrinsically safe installations. In most

cases, if an IS barrier is used, the filter will not be

needed.

Specifications

Typical specifications for the HF300 Series HART

filters are shown in table 1.

Note

Neither Emerson, Emerson Process

Management, nor any of their affiliated

entities assumes responsibility for the

selection, use, and maintenance of any

product. Responsibility for the

selection, use, and maintenance of any

product remains with the purchaser