Product Data Document

420DS-6d /

D301311X012

June 2011 - Page 6

ControlWave

®

Express

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

High Speed Counters

Number of points: 2 selectable as HSC or DI

Frequency Range: 0-10 kHz

Input Voltage Range:

Internally sourced: 3.3 Vdc
Externally sourced: 3 Vdc to 24 Vdc
On state: >1.65 V, Off state <1.65 V

Input filter: 20 microSec for 10 kHz

1 ms for 300 Hz LSC
Input current : selectable 200 µA for low

power applications or 2.2 mA for in-plant noise

immunity
Accumulator: 16 bit

Power consumption:

200 µA input, all inputs ON: 0.004 watt
2.2 mA input, all inputs ON: 0.039 watt

OpenBSI

Simply Creative

Emerson’s OpenBSI (

Open Bristol System Inter-

face) is a set of network setup, communication diag-

nostic, and data viewing utilities that provide access

to ControlWave controllers, flow computers and

RTUs. OpenBSI is the only product available in the

industry to bring such unique functionality and ease

of use to the network level. At the core is the com-

munication interface, written as a Windows com-

munication server API through which other client

applications communicate with the Bristol networks.

OpenBSI supports both serial BSAP protocol

and Ethernet Internet Protocol communication to

ControlWave controllers, flow computers and RTUs.

OpenBSI Utilities

Above this communication layer are a group of ap-

plications known as OpenBSI Utilities. These client

utilities communicate through the server to collect

and manage data gathered from the network, gen-

erate files based on collected historical data, collect

alarms, and monitor and control OpenBSI commu-

nications.

Communication engine for PC applications

Supports ControlWave serial and IP protocols

RS 232, Dial-line, cellular, radio, satellite, and

Ethernet connections
Provides on-line download & signal variable

changes
Allows network configuration through NetView

PC and Network communication diagnostics

OPC Server for interfacing to most HMI

software
Harvester collects historical data on request or

scheduled basis

NetView is the basic configuration and application

interface for all network operations. NetView uses

a tree structure for network graphical display in the

Windows Explorer style. Network nodes can be

Netview - Network configuration