D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

• Observe all required air space clearances to combustible materials as shown in Figure 6.2.
• Framing across the top of fi replace must be above top standoffs.

B

C

A

2 in. (51 mm)
min. air space
clearance
from chimney.

Header MUST NOT be notched!

D

D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.

Figure 6.4 Framing the Fireplace

C. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) (may be 24 in) from the fi replace

opening.

• Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed per Figure 6.3.

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Model #

A

B*

C**

D

A36

in.

43

23

41 1/2

8

mm

1092

584

1054

203

A42

in.

49

23

41 1/2

8

mm

1245

584

1054

203

* If interior of chase will be drywalled, add the thickness to this measurement.

** Adjust header height for a raised fl oor under fi replace.

Model #

A

Fireplace Opening

B

Outside Dimensions

A36

in.

36

42

mm

914

1067

A42

in.

42

48

mm

1067

1219

Heatilator • A36R & A42R • 28376 • Rev AF • 11/08