PRODUCT DATA

60-2309-13

V4055A,B,D,E

On-Off Fluid Power Gas

Valve Actuator

APPLICATION

The V4055 Gas Valve Actuator, in combination with a

VE5000

a

, V5055 or V5097 Gas Valve, controls the gas supply

to commercial and industrial burners.

When replacing a V4034 with a V4055, the V5034 gas valve

must also be replaced with a V5055 or V5097 gas valve.

FEATURES

• The V4055 Actuator, when used with the VE5000

a

,

V5097 or V5055 Valve, is rated for final safety shutoff

service.

• The V4055 Actuator can be used with the characterized

guide model of the V5055 or V5097 Gas Valve to

enhance lightoff smoothness.

• The standard model has an opening time of 26

seconds at 60 Hz or 32 seconds at 50 Hz. A fast-

opening model is available with timings of 13 seconds

at 60 Hz or 16 seconds at 50 Hz.

• Maximum closing time is one second, which meets

code, standard and insurer requirements.

• Models available with damper shaft, with or without

spring return; shaft extends out both sides and rides in

Teflon-like Delrin bushings; used with standard

7616BR Damper Crank Arm.

• Red OPEN indicator attached to actuator stem shows

when valve is even slightly open; yellow SHUT

indicator on valve stem shows only when gas valve is

fully closed.

• Models available with adjustable max flow limit switch.
• Ambient temperature rating is -40°F to +150°F (-40°C to

+66°C) for 60 Hz models and -10°F to +158°F (-23°C to

+70°C) for 50 Hz and 50/60 Hz models.

• Valve and actuator combinations can be mounted in

any position, with the exception of the 220 to 240 Vac,

50/60 Hz models, which are mounted vertically.

• Models available with factory-installed single pole

double throw (spdt) field-adjustable Auxiliary Switch.

Field-addable Auxiliary Switch kits are also available.

• Standard enclosure meets NEMA 1 (IP30)

requirements; models available with NEMA 4 (IP54)

weatherproof enclosure.

• V4055D and high pressure V4055E with Proof-of-

Closure Switch and V5055/V5097C or E with valve seal

overtravel interlock (double seal) to meet specific

code, standard and insurer requirements.

a

VE5000 is a European manufactured and approved valve for

European use only.

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

4

Wiring ...............................................................................

6

Checkout and Service ......................................................

7

Advertising