Caution, Recycling notice, Installation – Honeywell Q674F User Manual

Page 2: Operation

Advertising
background image

69-0435—10

2

IMPORTANT: Thermostats are calibrated at the factory by

using subbases mounted at true level. Inaccurate sub-
base leveling will cause thermostat control deviation.

LOCATION

Install the thermostat about 5 ft [1.5 m] above the

floor in an area with good air circulation at average
temperature.

Do not install the thermostat where it can be affected

by:

• drafts, or dead spots behind doors and in cor-

ners.

• hot or cold air from ducts.
• radiant heat from sun or appliances.
• concealed pipes and chimneys.
• unheated (uncooled) areas such as an outside

wall behind the thermostat.

MOUNTING THE SUBBASE

The thermostat subbase can be mounted on a vertical

outlet box, horizontal outlet box or directly on the wall.

1. If you must mount the subbase on a vertical outlet

box, order 193121A (beige) or 202689A (gray) Adapter
Assembly. See Fig. 1. The assembly includes an adapter ring,
two screws and a cover plate to cover marks on the wall. Install
the ring and cover plate on the vertical outlet box.

For a wall installation, hold subbase in position and

mark holes for anchors. See Fig. 2. Obtain wall anchors
locally. Set subbase aside. Drill four 3/16 in. [5 mm] holes
and gently tap anchors into the holes until flush with the wall.

2. Run wires to the thermostat location. See wiring

diagrams, Figs. 5-11.

Fig. 1—Installation of Q674 Subbase on outlet
box.

M925

VERTICAL
OUTLET
BOX

ADAPTER
RING

SUBBASE

COVER
PLATE

MOUNTING
SCREWS (2)

MOUNTING
SCREWS (2)

1

SUBBASE

MOUNTING
SCREWS (2)

HORIZONTAL
OUTLET
BOX

1

2

2

1 NOT INCLUDED WITH UNIT.

2 ACCESSORY PARTS AVAILABLE (193121A).

Recycling Notice

This control contains mercury in a sealed tube. Do not

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mercury

in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for

instructions regarding recycling and the proper disposal
of this control, or of an old control containing mercury in
a sealed tube.

M3375

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to

follow them could cause a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

1. Disconnect power supply to prevent electri-

cal shock or equipment damage.

2. To prevent interference with the thermostat

linkage, keep wire length to a minimum and
run wires as close as possible to the subbase.

3. Do not overtighten thermostat captive mount-

ing screws because damage to subbase threads
can result.

4. Do not short across coil terminals on relay. This

may burn out the thermostat heat anticipator.

5. Never install more than one wire per termi-

nal unless factory-supplied jumper with spade
terminal is used.

!

Operation

On a 2-stage heating thermostat, the two stages of heat

make sequentially as the temperature drops. Make refers to
the mercury switch initiating a call for heat or cool.

There are about 2

° F [1° C] between stages so the

sec-ond stage makes only when the first stage cannot
handle the load. This 2

° F [1° C] is referred to as the

interstage differential.

The LED indicators are light emitting diodes on the

subbase that light up when something specific happens
within the system. When an LED lights up, refer to the
following list for the meaning:

EM.HT.: Emergency heat is operating, which means

the system switch is at EM. HT.

AUX.HT.: Auxiliary heat is operating, which means

the weather is so cold that the heat pump can not
handle the load alone.

CHECK: System needs to be checked. See Heating/

Cooling System Instructions for specific meaning.

LEDs are not field replaceable or addable.