J6 and J16 Wiring Chart (cont.)

kW

Volt

Ph

Unit

Amp

Draw

Branch

Amp

Draw

Phase-

Phase

Resistance

(Ohms)

Min.
Feed

Breaker

or Fuse

Size

Internal

Power

Wire

Size

Element

Jumper

Wire

Size

Copper

Power Feed

Wire Size

Conduit

Size

Diagram

208

1

195.0

65.0

1.1

245

8

10

250

2"

6A

208

3

112.6

56.3

2.1

145

8

10

1/0

1¼"

12(NCB)

240

1

168.8

56.3

1.4

215

8

10

250

1½"

6A

240

3

97.4

48.7

2.8

125

10

12

1

1"

12(NCB)

380

3

60.8

60.8

7.1

80

8

10

3

1"

13(WT)

480

3

48.7

48.7

11.4

65

8

10

4

¾"

13(WT)

600

3

36.2

36.2

19.1

50

10

12

8

¾"

15

208

3

119.1

59.5

1.9

150

8

10

2/0

1¼"

12(NCB)

240

1

187.5

62.5

1.3

235

8

10

250

2"

6A

240

3

108.3

54.1

2.6

140

8

10

1/0

1¼"

12(NCB)

380

3

68.6

34.3

6.4

90

12

12

2

1"

12(WT)

480

3

54.1

54.1

10.2

70

8

10

4

¾"

13(WT)

600

3

42.2

42.2

16.4

55

10

12

6

¾"

15

208

3

149.9

74.9

1.6

190

6

8

3/0

1½"

12

240

3

129.9

65.0

2.1

165

8

10

2/0

1½"

12

380

3

80.0

40.0

5.3

100

10

12

1

1"

12(WT)

480

3

65.0

65.0

8.5

85

8

10

4

1"

13(WT)

600

3

54.3

54.3

12.8

70

8

10

4

1"

15

208

3

159.9

79.9

1.5

200

6

8

4/0

1½"

12

240

3

140.7

70.4

2.0

180

6

8

2/0

1½"

12

380

3

91.4

45.7

4.9

115

10

12

1

1"

12(WT)

480

3

70.4

35.2

7.9

90

12

12

3

1"

12(WT)

600

3

54.3

54.3

12.3

70

8

10

4

1"

15

64

208

3

178.6

59.5

1.4

225

8

10

4/0

1½"

17

66

600

3

63.4

63.4

10.9

80

8

10

4

¾"

18

240

3

162.4

54.1

1.7

205

8

10

4/0

1½"

17

380

3

102.8

34.3

4.2

130

12

12

1/0

1¼"

16(WT)

480

3

81.2

27.1

6.8

105

12

12

2

1"

16(WT)

79

380

3

120.0

40.0

3.7

150

10

12

2/0

1¼"

16(WT)

208

3

224.8

74.9

1.1

285

6

8

300

2"

17

240

3

194.9

65.0

1.4

245

8

10

250

2"

17

480

3

105.5

35.2

5.7

135

12

12

1

1"

16(WT)

85

600

3

81.5

81.5

8.5

105

6

8

2

1"

18

86

208

3

239.8

79.9

1.0

300

6

8

350

2"

17

240

3

211.1

70.4

1.3

265

6

8

300

2"

17

480

3

105.5

35.2

5.2

135

12

12

1/0

1¼"

16(WT)

90

380

3

137.1

45.7

3.2

175

10

12

2/0

1½"

16(CBWT)

88

58.5

40.5

45

54

68

81


J6 and J16 Wiring Chart Notes:
1. Power feed wire sizing is based on using 75°C Cu THHN wire with feeder branch

protection rated at 125%.

2. Internal wire sizing is based on using 200°C SEW-2 or PTFE wiring in a raceway

with an ambient temperature up to 60°C.

3. For information on 277V, 415V, or 440V models reference the supplied drawing

or contact the factory.

4. Normal phase-to-phase resistance tolerance is ±5%.
5. 380, 480, and 600-volt phase-to-phase resistance values are shown with the transformer

disconnected.

6. For 575V models, multiply the kW rating of the 600V model by a de-rating factor of 0.92

to get the actual rating for 575V.

7. For models manufactured prior to June 24, 2005, that utilize wiring diagrams 3, 5, 6,

7(NT), 7(WT), or 11 please contact the factory for wiring diagrams.