Troubleshooting guide, Setting keypad lockout switch – Honeywell SERIES 2000 T7300D User Manual

Page 8

Advertising
background image

62-0132

8

T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT

ON

1

2

M10235

BACK OF THERMOSTAT

1

2

1

2

DIP 1 IS ON

DIP 2 IS NOT USED.

5. Press the increase

key again to display the

EEPROM identification code. (Example: 314=
EEPROM ID 314)

6. Press the increase

key again to display the

subbase identification code. (Example: C=
conventional subbase)

M4933A

7. Press Run Program to exit the system test. The

system test times out after four minutes without any
key presses.

Setting Keypad Lockout Switch

The DIP switch 1 on the back of the thermostat activates
the lockout feature. The switch must be set to the ON
position (up) to activate the lockout feature. See Fig. 7.

The factory-setting is off (down). Remove the thermostat
from the subbase and set the switch to ON if keypad
lockout is desired. Setting DIP switch 1 to the ON position
disables all of the keys on the thermostat.

M10289

(continued)

Fig. 7. Setting the keypad lockout DIP switch 1

on the back of the thermostat.

NOTE:

DIP switch 1 should be set to ON prior to entering
Installer setup. This only applies when changing
Installer setup number 25 or 40.

Symptom

Possible Cause

Action

Display will not
come on.

Thermostat is not being
powered.

Check that X terminal is connected to the system
transformer.

Check for 24 Vac between X and R or RH terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the
circuit breaker.

check if the system fuse is blown—replace the
fuse.

check if the power switch on the HVAC
equipment is in the Off position—set to the On
position.

check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Temperature display
is incorrect.

Room temperature display
has been reconfigured.

Enter Installer Setup number 37 and reconfigure the display.

Thermostat is configured for
°F or °C display.

Enter Installer Setup number 14 and reconfigure the display.

Bad thermostat location.

Relocate the thermostat.

Display shows two dashes
and a degree sign.

Installer Setup 22 is set for remote sensing and the sensor is
missing or the circuit is open or shorted.

Temperature settings
will not change.
(Example: Cannot

Upper or lower temperature
limits were reached.

Check the temperature setpoints:

Heating limits are 40 to 90°F (7 to 31°C)

Cooling limits are 45 to 99°F (9 to 37°C)

set heating higher or
cooling lower.)

The setpoint temperature
range stops were configured.

Check Installer Setup number 34 and 35 and reconfigure the
setpoint stops.

Keypad is locked. When a
locked key is pressed, LOC
will flash on the LCD.

Reset DIP switch 1 on back of thermostat to enable
keypad.

TROUBLESHOOTING GUIDE