Installation and operations manual, Operational check out, Evaporator superheat – Heatcraft Refrigeration Products Unit Coolers H-IM-UC User Manual

Page 6

Advertising
background image



Installation and Operations Manual

Operational Check Out

After the system has been charged and has operated for at least

two hours at normal operating conditions without any indication of

malfunction, it should be allowed to operate overnight on automatic

controls. Then a thorough recheck of the evaporator operation should

be made as follows:

(a) Check liquid line sight glass and expansion valve operation.

If there are indications that more refrigerant is required,

leak test all connections and system components and repair

any leaks before adding refrigerant.

(b) Thermostatic expansion valves must be checked for

proper superheat settings. Feeler bulbs must be in positive

contact with the suction line and should be insulated. Valves

set at high superheat will lower refrigeration capacity.

Low superheat promotes liquid slugging and compressor

bearing washout.

(c) Check defrost controls for initiation and termination

settings, and length of defrost period. Set fail safe at

length of defrost + 25%.

Example: 20 minute defrost + 5 minutes

= 25 minute fail safe

(d) Check drain pan for proper drainage.

(e) Install instruction card and control system diagram for

use of building manager or owner.

Evaporator Superheat

Check Your Superheat. After the box temperature has reached or is

close to reaching the desired temperature, the evaporator superheat

should be checked and adjustments made if necessary. Generally,

systems with a design TD of 10

˚

F should have a superheat value of 6

˚

to 10

˚

F for maximum efficiency. For systems operating at higher TD’s,

the superheat can be adjusted to 12

˚

to 15

˚

˚F as required.

NOTE:

Minimum compressor suction superheat

of 20˚F may override these recommendations

on some systems with short line runs.

To properly determine the superheat of the evaporator, the following

procedure is the method Heatcraft recommends:

WARNING: If the condensing unit has no flooded

condenser head pressure control, the

condensing unit must have the discharge

pressure above the equivalent 105˚F

condensing pressure.

1. Measure the temperature of the suction line at the point

the bulb is clamped.

2. Obtain the suction pressure that exists in the suction line

at the bulb location by either of the following methods:

a. A gauge in the external equalized line will indicate the

pressure directly and accurately.

b. A gauge directly in the suction line near the

evaporator or directly in the suction header of the

evaporator will yield the same reading as 2a above.

3. Convert the pressure obtained in 2a or 2b above to

saturated evaporator temperature by using a

temperature-pressure chart.

4. Subtract the saturated temperature from the actual

suction line temperature. The difference is Superheat.

Alternative Superheat Method

The most accurate method of measuring superheat is found by

following the previous procedure, Temperature/Pressure method.

However, that method may not always be practical. An alternative

method which will yield fairly accurate results is the temperature /

temperature method:

1. Measure the temperature of the suction line at the

point the bulb is clamped (outlet).

2. Measure the temperature of one of the distributor

tubes close to the evaporator coil (inlet).

3. Subtract the inlet temperature from the outlet

temperature. The difference is Superheat.

This method will yield fairly accurate results as long as the pressure

drop through the evaporator coil is low.

Figure . Bulb and Contact Location

Figure 7. Multiple Evaporators

Advertising